2006-03-22 00:00:00BUILDING REVIEW CHECKLIST:
 1- AFTER CORRECTIONS ARE DONE TO THE
 ORIGINAL DRAWINGS, TAKE THEM TO PALM
 BEACH COUNTY BUILDING TO PAY THE IMPACT
 FEES. BRING STAMPED DRAWINGS & RECEIPT.
  
 2- NEED RECORDED NOTICE OF COMMENCEMENT.
  
 3- PROVIDE SOIL TEST REPORT. (2 COPIES).
  
 4- SPECIFY SAFETY GLASS FOR WINDOW IN
 MASTER BATHROOM SHOWER AS REQ'D BY SEC.
 R308.4 2004 RESIDENTIAL CODE.
  
 5- SPECIFY ATTIC SIZE AS REQUIRED BY
 SEC. R807 2004 RESIDENTIAL CODE.
  
 6- REVISE STRUCTURAL NOTE #14: A) 1 3/4"
 NAIL IS TOO SHORT. NEED 1 3/4" MIN.
 PENETRATION INTO THE WOOD TRUSSES. SEE
 COPY OF ASTM C1063 ATTACHED.
 B) STUCCO HAS NOTHING TO DO WITH
 VENTILATION. THESE ARE 2 DIFFERENT
 ISSUES. REVISE NOTE AS REQUIRED.
  
 7- OWES $317.87 FOR UPDATED VALUATION
 AND RADON FEES.
  
 8- PROVIDE CALCULATIONS FOR DOOR AND
 WINDOWS DESIGN PRESSURES SHOWN ON PLANS.
 DESIGN PRESSURS SHOWN FOR SOME OPENINGS
 ARE LOWER THAN THOSE SHOWN ON FIGURE
 R301.2(8) OF 2004 RESIDENTIAL CODE.
 ALSO, PROVIDE CORRECT DESIGN PRESSURES
 FOR OPENINGS LOCATED IN THE END ZONE.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
  
 9- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR SIMPSON CONNECTOR VTC 2
 SHOWN ON DETAIL D-D, DWG 2 OF 4.
  
 10- ALL PRODUCT APPROVALS NEED TO BE
 REVIEWED AND APPROVED IN WRITTING (TYP.
 DONE USING THE STANDARD REVIEW STAMP) BY
 THE ENGINEER OF RECORD PRIOR TO
 SUBMITTAL TO THIS OFFICE AS REQUIRED BY
 SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004
  
 11- SPECIFY 2 LAYERS OF UNDERLAYMENT FOR
 3:12 PITCH AS REQUIRED BY SEC. R905.2.7
 2004 RESIDENTIAL CODE.
  
 12- CONNECTOR FGTR. SEE CATALOGUE FOR
 SPECIFIED FASTENER. PROVIDE ENGINEERING
 CALCS FOR FASTENERS THAT DIFFER FROM
 THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 13- ENERGY CALCULATIONS: A) USE 2004
 FORM, NOT 2001.
 B) CEILING FAN CREDIT WAS TAKEN.
 THEREFORE, SPECIFY CEILING FANS SIZES IN
 ELECTRICAL PLAN AS REQUIRED BY TABLE
 13-607.1.A.1 FBC 2004.
  
 14- A)CLARIFY IF USING DOORS AND WINDOWS
 WITH HURRICANE MISSILE IMPACT GLAZING OR
 NOT. PRODUCT APPROVALS SUBMITTED ARE FOR
 WINDOWS WITH IMPACT GLAZING, BUT PRODUCT
 APPROVAL FOR DOORS SUBMITTED IS FOR
 NON-IMPACT GLAZING.
 IF USING SHUTTERS, THEN, PROVIDE KEY
 PLAN AND A COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED SAMPLE AND
 COMPLETE ALL THE INFORMATION.
 B) IF USING FRENCH DOORS WITH IMPACT
 GLAZING, THEN PROVIDE CORRESPONDING
 FLORIDA PRODUCT APPROVAL.
  
 15- ENGINEER TO SPECIFY ALL LIVE LOADS
 AND DEAD LOADS FOR ROOF TRUSSES. SEE
 TABLE R301.5 FOR MIN. LIVE LOADS
 REQUIRED. DEAD LOADS NEED TO CONSIDER
 THE ACTUAL WEIGHT OF MATERIALS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 16- PROVIDE SECTION/DETAIL SHOWING HOW
 ARE ROOF TRUSSES ATTACHED TO EXISTING
 EXTERIOR BEARING WALL. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 17- PREFABRICATED WOOD TRUSSES AND
 GIRDERS NOTE #1 NEED TO BE REVISED.
 REFERENCE THE RESIDENTIAL CODE. SEE SEC.
 R802.10 2004 RESIDENTIAL CODE.
  
 18- ROOF FRAMING PLAN: WHAT OR WHERE IS
 DETAIL D 2/3?.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (5610805-6712