| Plan Review Notes For Permit 06020892 |
| Permit Number |
06020892 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-04-25 00:00:00 | *** DENIED *** | | | 1) ENGINEER'S NAME, ADDRESS, AND LICENSE | | | NUMBER MUST BE LEGIBLY INDICATED ON ALL | | | PLANS THAT HAVE HIS SEAL ON THEM, PER | | | FAC 61G15-23.002 . | | | | | | 2) RETURN AIR DUCTS TO BEDROOMS DO NOT | | | RETURN TO TRUNK LINE OR A/C UNIT PLEASE | | | CORRECT. | | | | | | 3) RETURN AIR TRUNK LINE TO AIR HANDLER | | | UNIT IS NOT SIZED. | | | | | | 4) MANUAL J CAL'S. ARE SHOWING 110 | | | CFM'S. TO EACH AND EVERY ROOM REGARDLESS | | | OF ROOM SIZE PLEASE CORRECT. | | | | | | 5) MANUAL J CAL'S. DO NOT SHOW NAME OF | | | ROOMS AND NEED TO. | | | | | | 6) MECHANICAL PLANS CFM'S. TO EACH ROOM | | | AND MANUAL J CAL'S. CFM'S. TO EACH ROOM | | | DO NOT MATCH PLEASE CORRECT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|