Plan Review Notes
Plan Review Notes For Permit 06020892
Permit Number 06020892
Review Stop M
Sequence Number 2
Notes
Date Text
2006-04-25 00:00:00*** DENIED ***
 1) ENGINEER'S NAME, ADDRESS, AND LICENSE
 NUMBER MUST BE LEGIBLY INDICATED ON ALL
 PLANS THAT HAVE HIS SEAL ON THEM, PER
 FAC 61G15-23.002 .
  
 2) RETURN AIR DUCTS TO BEDROOMS DO NOT
 RETURN TO TRUNK LINE OR A/C UNIT PLEASE
 CORRECT.
  
 3) RETURN AIR TRUNK LINE TO AIR HANDLER
 UNIT IS NOT SIZED.
  
 4) MANUAL J CAL'S. ARE SHOWING 110
 CFM'S. TO EACH AND EVERY ROOM REGARDLESS
 OF ROOM SIZE PLEASE CORRECT.
  
 5) MANUAL J CAL'S. DO NOT SHOW NAME OF
 ROOMS AND NEED TO.
  
 6) MECHANICAL PLANS CFM'S. TO EACH ROOM
 AND MANUAL J CAL'S. CFM'S. TO EACH ROOM
 DO NOT MATCH PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.