 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE INDICATE THE AIC RATING OF THE
 EQUIPMENT PER 110.9 & 110.10.
  
 2} THE CURRENT NEC CYCLE IS 2002. SEE
 NOTE #1.
  
 3} BEDROOMS 1,3,4 AND LIVING ROOM NEED
 RECEPTACLES ADDED TO COMPLY WITH
 210.52(A)(1)&(2). SEE REVIEWED SET OF
 PLANS.
  
 4} THE RECEPTACLE ON THE KITCHEN ISLAND
 MUST COMPLY WITH 210.8(A)(6)
  
 5} A RECEPTACLE MUST BE LOCATED OUTSIDE
 AT THE FRONT OF THE RESIDENCE TO COMPLY
 WITH 210.52(E).
  
 6} THE OCP FOR THE AHU @ 80 (CIRCUIT
 1/3), IS TOO LARGE FOR THE #6 CONDUCTOR,
 SEE 210.16.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  