| Plan Review Notes For Permit 06020892 |
| Permit Number |
06020892 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-13 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE INDICATE THE AIC RATING OF THE | | | EQUIPMENT PER 110.9 & 110.10. | | | | | | 2} THE CURRENT NEC CYCLE IS 2002. SEE | | | NOTE #1. | | | | | | 3} BEDROOMS 1,3,4 AND LIVING ROOM NEED | | | RECEPTACLES ADDED TO COMPLY WITH | | | 210.52(A)(1)&(2). SEE REVIEWED SET OF | | | PLANS. | | | | | | 4} THE RECEPTACLE ON THE KITCHEN ISLAND | | | MUST COMPLY WITH 210.8(A)(6) | | | | | | 5} A RECEPTACLE MUST BE LOCATED OUTSIDE | | | AT THE FRONT OF THE RESIDENCE TO COMPLY | | | WITH 210.52(E). | | | | | | 6} THE OCP FOR THE AHU @ 80 (CIRCUIT | | | 1/3), IS TOO LARGE FOR THE #6 CONDUCTOR, | | | SEE 210.16. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|