Plan Review Notes
Plan Review Notes For Permit 06020842
Permit Number 06020842
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-24 00:00:00******** UNSAT **********
  
 1)NOTE: PLEASE CORRELATE PANEL "A' WITH
 RISER ETC AS NOTE ON PANEL "A" MENTIONS
 TO BE 200A, YET RISER SHOWS THIS A 150A?
  
 2)NOTE: PLEASE SEE MIN SIZE GROUNDING
 ELECTRODE CONDUCTOR SHALL BE 1/0, NOT #1
 ASSHOWN.
 250.66,310.15B6
 ** PLEASE KNOW, GROUNDING ELECTRODE IS
 SHOWN GOING TO CWP, HOWEVER THIS IS
 NOTED AS PVC?
  
 3)NOTE: PLEASE SEE SD REFERENCES THE
 WRONG CHAPTER, AS THE NFPA-72 UNDER
 CURRENT AOPTION IS THE 2002 -720, PLEASE
 KNOW, THIS WAS OF JAN 1ST, 2005.
 PLEASE SEE CHAPTER 11, UNDER THE 2002
 NFPA-72.
  
 4)NOTE: PLEASE SEE DISHWASHER IS BEING
 SHOWN AS A 2POLE/240V UNIT? PLEASE
 VERIFY AS RECEPTS ON PLANS SEEM TO
 INDICATE A DISPOSAL, YET PANEL SCHEDULE
 DOES NOT SHOW THIS.
 PLEASE VERIFY AND CORRELATE.
  
 5)NOTE: PLEASE SEE THREE CU'S ON PLANS,
 YET ONLYTWO DISC'S SHOWN.
 440.11
  
 6)NOTE: PLEASE SEE REDLINED MISSING
 RECEPTS PER 210.52, LIV RM, BEDRM #3.
  
 7)NOTE: PLEASE SEE 2KW LOAD FROM HI-HATS
 IS BEING SHOWN ON ONE CIRCUIT. PLEASE
 KNOW THE LOAD FOR A 15A CIRCUIT IS
 1440VA.
  
 ** PLEASE REMOVE ANY OLD/VOIDED SHEETS
 AND ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]