| Plan Review Notes For Permit 06020814 |
| Permit Number |
06020814 |
|
| Review Stop |
E |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2007-05-11 13:45:37 | ** UNSAT ** | | | | | | ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA | | | BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED | | | BY THE CITY OF WEST PALM BEACH. | | | | | | | | | | | | 1) NOTE:PLEASE SEE THAT ANY TRANSFER TYPE DEVICE OR | | | EQUIPMENT MUST PROVIDE A FAIL SAFE OPERATION SO THAT NO | | | INADVERTENT CONNECTION CAN BE DONE FROM EITHER THE | | | UTILITY OR BACK UP POWER SOURCE. | | | PLEASE KNOW THAT EXTENDED CONVERSATIONS WITH UL, NEMA | | | ANDNUMEROUS MANUFACTURES AND OTHER JURISDICTIONS ON | | | TO STATE AND NATIONAL LEVEL HAS ALREADY TAKEN PLACE AND | | | THIS SPECIFIC DEVICE DOES NOT MEET THE CODE OR PROVIDE | | | THE REQUIRED ACTION BY THE NEC AND CAN NOT BE ACCEPTED | | | BY THIS AHJ. | | | 110.3, 702.6. | | | PLEASE SUBMIT THE MANUFACTURE SPEC/CUT SHEETS FOR THE | | | NEW EQUIPMENT WHICH WILL PROVIDE THIS OPERATION. 110.3, | | | 90.7, 100, 702.5 | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|