| 2006-10-18 10:34:30 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB |
| | FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH AMENDMENTS TO THE |
| | FBC2004 |
| | |
| | |
| | 1.)A NOTICE OF COMMENCEMENT WILL BE REQUIRED PRIOR TO |
| | PERMIT PICKUP, FS713.13. |
| | |
| | 2.)FROM PREVIOUS REVIEWS, FLORIDA STATE OR LOCAL |
| | PRODUCT APPROVAL REQUIRED FOR THE BULLET PROOF GLASS. |
| | THE MIAMI-DADE NOA IS NO LONGER A PART OF THE PACKAGE. |
| | IT IS UNCLEAR HOW THE ENGINEER HAS DETERMINED A DESIGN |
| | PRESSURE OF -71 AFTER REMOVING THE STRESS INCREASE FOR |
| | STEEL (STARTING AT A DP OF -94) WHEN THE DP ON THE NOA |
| | IS +-50.ALL ADDITIONAL ENGINEERING SUBMITTED IS TO BE |
| | SIGNED, SEALED DATED ORIGINALS (PHOTOCOPIES PROVIDED). |
| | A SECTION OF THE FBC2001 WAS PROVIDED; YOU MUST SHOW |
| | CODE COMPLIANCE WITH FBC2004.THE ENGINEER'S TITLE |
| | BLOCK IS TO COMPLY WITH ALL REQUIREMENTS OF |
| | FAC61G15-23.002. |
| | |
| | 3.)THE ALUMINUM LIGHTING POLES SPECIFY ASCE7-98 AND |
| | "FLORIDA BUILDING CODE".DECLARE GOVERNING CODE |
| | (FBC2004) AND SEE FBC35, INCORRECT ASCE VERSION |
| | (ASCE7-02). |
| | |
| | 4.)WHEN RESUBMITTING, HAVE THE DUMPSTER ENCLOSURE |
| | PERMIT APPLICATION PROCESSED AT THE FRONT DESK.THE |
| | CONTRACTOR'S SIGNATURE MUST BE EITHER NOTARIZED OR |
| | VERIFIED IN PERSON.PLEASE CONTACT ME IF YOU NEED |
| | FURTHER ASSISTANCE. |