| Plan Review Notes For Permit 06020814 |
| Permit Number |
06020814 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-08-07 00:00:00 | DENIED: | | | FIRST PLAN REVIEW BY HAROLD MOSER | | | 4-3-06, ALL COMMENTS ADDRESSED. | | | | | | 1.PLAN SHEET M-2 VENTILATION | | | CALCULATION REFERS TO ASHRAE 62-89 THIS | | | SHOULD READ ASHRAE 62-01. | | | | | | 2.PLAN SHEET M-2 OCCUPANCY | | | CLASSIFICATION PLAN INDICATES | | | COMMERCIAL, THIS SHOULD READ BUSINESS | | | ACCORDING TO 2004 FBC 304.1. | | | | | | 3.PLAN SHEET M-2 MECHANICAL NOTE #4 | | | INDICATES DUCT SMOKE DETECTOR FOR FAN | | | SHUTDOWN.PLEASE NOTE, FAN SHUTDOWN | | | SHALL ALSO COMPLY WITH 606.4.1 THE DUCT | | | SMOKE DETECTOR SHALL ACTIVATE A VISIBLE | | | & AUDIBLE SUPERVISORY SIGNAL AT A | | | CONSTANTLY ATTENDED LOCATION OR COMPLY | | | WITH EXCEPTION 1 OR 2. | | | | | | PLANS DO NOT INDICATE IF THE VAULT HAS A | | | FIRE RESISTANCE RATING.PLEASE CLARIFY. | | | SHOULD CEILING TO THE VAULT BE RATED A | | | CEILING DAMPER WILL BE REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | | E-MAIL [email protected]. | | | |
|