| 2006-06-24 00:00:00 | *** UNSAT 2ND REVIEW *** |
| | |
| | ** PLEASE SSE SOME COMMENTS FROM |
| | PREVIOUS REVIEW AND SEE ALSO NEW NOTE |
| | NOT ON PREVIOUS REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE TITLE BLOCKS ON |
| | PLANS SHALL CONTAIN THE ADDRESS OF |
| | BUILDING/SITE. PLEASE SEE THE RESPONSE |
| | MENTIONS THIS WAS ADDED TO NORTH |
| | ELEVATION, HOWEVER THIS IS REQUIRED ON |
| | ALL SHEETS AND FOR ALL TRADES. |
| | 61G1-16.004,61G15-23.002 |
| | PREVIOUS REVIEW. |
| | |
| | 2) NOTE: PLEASE SEE SHEETS SIGNED AND |
| | SEALED BY KILDAY AND ASSOCIATES AND |
| | NEIL, SMITH AND ASSC. |
| | PLEASE SEE MISSING REQUIRED INFORMATION |
| | ON TITLE BLOCKS AS MENTIONED ON PREVIOUS |
| | REVIEW. |
| | THESE ARE MISSING THE PRINTED NAME AND |
| | LICENSE NUMBERS, AND CERTIFICATE OF |
| | AUTHORIZATION #S' . |
| | PLEASE KNOW, NEIL AND ASSC IS MISSING |
| | THE CA# AND KILDAY AND ASSC IS MISSING |
| | PRINTED NAME, AND CA #. |
| | 61G1-16.004, FS 481.219 |
| | |
| | 3) NOTE: PLEASE SEE THAT NO WIND LOAD |
| | CALCULATIONS SIGNED, DATED AND SEALED |
| | WERE SUBMITTED FOR LT POLE/SITE LTS. |
| | PREVIOUS REVIEW |
| | |
| | ** NEW NOTE** |
| | |
| | 4) NOTE: PLEASE SEE ENERGY CALCULATIONS |
| | ARE REQUIRED TO BE SIGNED, DATED AND |
| | SEALED BY THE RESPONSIBLE DESIGNER(S). |
| | PLEASE KNOW, AS SUBMITTED THESE DO NOT |
| | SEEM TO COMPLY TO 2004 FBC CHAPTER 13, |
| | AS CALC SHEETSDO NOT SEEM TO INDICATE |
| | ALL LIGHTING AND AMOUNTS PERMITTED AND |
| | USED PER 13-415.1.AB.1 FOR MIN |
| | CALCULATIONS TO BE SHOWN, PLEASE ALSO |
| | SEE LIGHTING DENSITIES REQUIRED IN |
| | CALCULATIONS, 13-415.2.ABC.1 , ONLY ONE |
| | OF THE TWO METHODS ARE PERMITTED. |
| | PLEASE SEE TABLES. |
| | |
| | ** PLEASE SEE BUIIDING REVIEW COMMENTS |
| | AS PRODUCT APPROVALS SHOULD NOT BE |
| | ATTACHED TO PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |