| Date |
Text |
| 2006-05-10 00:00:00 | ******DENIED****** |
| | |
| | 1) PLEASE SEE COMMENTS REGARDING CORRECT |
| | ADDRESSING OF BUILDING. ADDRESS SHALL BE |
| | MINIMUM OF 6" IN HEIGHT AND CONTRASTING |
| | TO BACKGROUND. PLEASE ADD NOTE TO |
| | ELEVATIONS. |
| | |
| | 2) LIFE SAFETY NFPA 101, 2003 EDITION |
| | SHALL BE REFERENCED. |
| | |
| | 3) PLEASE PROVIDE CLARIFICATION |
| | REGARDING TRAVEL DISTANCE. IS THIS NOTE |
| | REFERENCING TRAVEL DISTANCE TO EXITS OR |
| | COMMON PATH OF TRAVEL? NFPA 101, |
| | SECTIONS 38.2.5 AND 38.2.6. |
| | |
| | 4) PLEASE INDICATE THE MINIMUM INTERIOR |
| | FINISH CLASSIFICATION FOR WALLS AND |
| | CEILINGS IN TERMS OF CLASS A,B OR C. |
| | |
| | 5) SHT M-2 MENTIONS A FIRE ALARM SYSTEM. |
| | (NOTE #4) DUCT SMOKE DETECTORS SHALL |
| | INITIATE A GENERAL FIRE ALARM IN |
| | ACCORDANCE WITH LOCAL REQUIREMENTS. |
| | WHERE NO FIRE ALARM IS PROVIDED, |
| | AUDIBLE/VISUAL DEVICES ARE STILL |
| | REQUIRED FOR OCCUPANT NOTIFICATION. |
| | |
| | 6) SEPARATE SHOP DRAWINGS AND PERMIT |
| | REQUIRED FOR FIRE ALARM SYSTEM. |
| | |
| | 7) PLEASE CLARIFY NOTE ON SHT E-5 IN |
| | REFERENCE TO MONITORING OF SMOKE |
| | DETECTORS. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |