| 2006-05-05 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)A NOTICE OF COMMENCEMENT MUST BE |
| | FILED WITH THE CLERK OF COURTS BEFORE A |
| | PERMIT CAN BE ISSUED, FS713.13. |
| | |
| | 2.)IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY.THE PLANS MUST BE STAMPED |
| | AND THE RECEIPT ATTACHED TO THE |
| | APPLICATION.561-233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 3.)PROVIDE A SURVEY FOR THIS PROPERTY, |
| | FBC*106.3.4.IF THE IMPROVEMENT CROSSES |
| | A PROPERTY LINE, A UNITY OF TITLE WILL |
| | BE REQUIRED.THE RECORDED UNITY OF |
| | TITLE MUST BE PROVIDED PRIOR TO PERMIT |
| | ISSUANCE. |
| | |
| | 4.)THE CONTRACTOR'S INSURANCE IS |
| | EXPIRED.PLEASE PROVIDE A CURRENT |
| | INSURANCE CERTIFICATE PRIOR TO PERMIT |
| | ISSUANCE. |
| | |
| | 5.)PROVIDE PRODUCT APPROVALS FOR THE |
| | COMPONENTS AND CLADDING.PRODUCT |
| | APPROVALS ARE TO BE REVIEWED BY THE |
| | DESIGNER OF RECORD, FBC*106.3.3. |
| | PROVIDE FOR ALL COMPONENTS AND CLADDING, |
| | INCLUDING |
| | |
| | IMPACT STOREFRONT |
| | HOLLOW METAL DOORS |
| | BULLET RESISTANT VISION WINDOW |
| | TILE ROOF, CIRCLE METHOD OF ATTACHMENT |
| | ON THE PRODUCT APPROVAL |
| | |
| | 6.)THE PLANS SHOW IMPACT GLASS.IF |
| | THIS IS CHANGED ON THE PLAN TO NON |
| | IMPACT WITH REMOVABLE SHUTTERS, BE |
| | ADVISED THAT USE OF REMOVABLE SHUTTERS |
| | ON COMMERCIAL BUILDINGS MUST BE APPROVED |
| | BY THE BUILDING OFFICIAL.IF THERE IS A |
| | CHANGE TO THE PLANS IN REGARDS TO IMPACT |
| | PROTECTION, FAILURE TO SUBMIT A |
| | HURRICANE SHUTTER INSTALLATION PLAN WILL |
| | CAUSE DELAYS IN PERMIT ISSUANCE.THIS |
| | ITEM IS INFORMATIONAL ONLY. |
| | |
| | 7.)INFORMATIONAL ONLY; SEPARATE |
| | PERMITS WILL BE REQUIRED FOR THE SCREEN |
| | WALL AND THE DUMPSTER ENCLOSURE. |
| | COMPLETE A PERMIT APPLICATION FOR THE |
| | DUMPSTER ENCLOSURE AND PROVIDE WITH THE |
| | RESUBMITTAL.SEPARATE PLANS ARE NOT |
| | NECESSARY. |
| | |
| | 8.)THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER FOR SOUTHERN DESIGN GROUP INC. IS |
| | REQUIRED TO BE ON EACH SHEET, |
| | FAC61G15-23.002. |
| | |
| | 9.)THE PARKING STRIPING IS TO COMPLY |
| | WITH THE CITY OF WEST PALM BEACH |
| | STANDARD, SEE ATTACHED DETAIL. |
| | |
| | 10.)DECLARE THE MEAN ROOF HEIGHT SO |
| | THAT MOMENTS OF RESISTANCE FOR THE ROOF |
| | TILE CAN BE DETERMINED. |
| | |
| | 11.)PROVIDE THE DISTANCE BETWEEN THE |
| | PROPOSED BANK AND THE EXISTING BUILDING, |
| | FBC TABLE 602.IF THEY ARE ON THE SAME |
| | LOT, SHOW THE ASSUMED PROPERTY LINE AND |
| | COMPLIANCE WITH TABLE 602. |
| | |
| | 12.)THE PROPERTY LINE IS NOT CLEAR ON |
| | THE SITE PLAN.IF THE SCREEN WALL 7-SP4 |
| | IS ALONG A PROPERTY LINE, SHOW THE |
| | PROPERTY LINE ON THE DETAIL.THE FOOTER |
| | CANNOT ENCROACH THE PROPERTY LINE.SEE |
| | SP1.SOME OF THE TEXT IS UPSIDE DOWN OR |
| | IN THE WRONG LOCATIONS.THERE IS A LINE |
| | SHOWING ?PROPOSED LEASE LINE? WHICH |
| | SEEMS TO INDICATE ONLY ONE PARCEL.A |
| | BOUNDARY SURVEY SHOULD HELP TO CLARIFY |
| | LOT LINES. |
| | |
| | 13.)A1 STATES THAT THERE IS A 75' MAX |
| | TRAVEL DISTANCE.DO YOU MEAN COMMON |
| | PATH OF TRAVEL FBC1013.3?THE TRAVEL |
| | DISTANCE EXCEEDS 75'.IF YOUR DESIGN |
| | INTENTION IS TO EXCEED CODE AND RESTRICT |
| | MAXIMUM TRAVEL DISTANCE TO 75' PLEASE |
| | REVISE THE PLANS.OTHERWISE REVISE THE |
| | 75' MAX TRAVEL DISTANCE REQUIREMENT |
| | FBC1015.1.NOTE THAT ONLY ONE EXIT IS |
| | REQUIRED FBC1014.1 SO THERE IS NO |
| | REQUIREMENT FOR COMMON PATH OF TRAVEL. |
| | IT IS ACCEPTABLE TO EXCEED CODE BUT THE |
| | PLANS SHOULD BE CONSISTENT WITH YOUR |
| | DESIGN SPECIFICATION. |
| | |
| | 14.)SHOW THE MANEUVERING CLEARANCE, |
| | PULL SIDE, FOR DOORS 104, 108, 112, |
| | FIGURE FBC 11-25, FBC11-4.13.6. |
| | |
| | 15.)BREAK ROOM SINK IS TO COMPLY WITH |
| | FBC11-4.24.SHOW ALL DIMENSIONS, |
| | INCLUDING KNEE CLEARANCE. |
| | |
| | 16.)THE TELLER COUNTER IS SHOWN AS |
| | 40IN.SEE FBC11-7.2(2) AND SHOW |
| | COMPLIANCE ON THE PLAN. |
| | |
| | 17.)S1 SHOWS DISTANCES OF 29FT (EAST |
| | WALL) AND 16FT (SOUTH WALL) BETWEEN |
| | GROUT FILLED CELLS.A 4FT DISTANCE IS |
| | MORE TYPICAL FOR CBS CONSTRUCTION.IF |
| | THIS IS AN ERROR, PLEASE REVISE THE |
| | PLANS.IF THIS IS NOT AN ERROR, PLEASE |
| | CONTACT ME TO DISCUSS. |
| | |
| | 18.)SIGN THE OWNER/AGENT LINE OF THE |
| | ENERGY CALC, FBC13-103.1. |
| | |
| | 19.)THE SQUARE FOOT AREA ON THE ENERGY |
| | CALCS IS 3250, THE PLAN IS 3594.THE |
| | TWO SHOULD BE CONSISTENT. |