Plan Review Notes
Plan Review Notes For Permit 06020800
Permit Number 06020800
Review Stop P
Sequence Number 4
Notes
Date Text
2009-02-09 10:23:23DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS P1, P2, P3 & P4 THE SIGNATURE OF THE ENGINEER
 OF RECORD DOES NOT MATCH THE SIGNATURE ON THE PLANS ON
 FILE FOR PUBLIC RECORD. PER FAC 61G15-23.002(1)(2) THE
 PROFESSIONAL ENGINEER SHALL SIGN HIS NAME. IT APPEARS
 THAT INITIALS HAVE BEEN USED TO SIGN THE REVISION
 SHEETS. PLEASE AFFIX THE SIGNATURE ON EACH SHEET. FS
 471.025.
  
 2. SHT P2 WATER RISER DIAGRAM. AIR CHAMBERS ARE NOT
 APPROVED. SECTION 604.9. WATER HAMMER ARRESTORS SHALL
 BE INSTALLED ON ALL QUICK CLOSING VALVES, (ICE MAKERS,
 DISH WASHERS, OR WASH MACHINES). IF WATER HAMMER
 ARRESTORS ARE INSTALLED, THEY SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE", NOT IN THE CEILING.
 PDI-WH 201.
  
 3. SHT P2 SANITARY RISER DIAGRAM DOES NOT REFLECT THE
 CHANGES SHOWN ON THE FLOOR PLAN. PLEASE CORRECT THE
 FOLLOWING:
 A. THE FIRST FITTING AND PIPING AS THE SANITARY ENTERS
 THE BUILDING WAS DELETED ON THE FLOOR PLAN BUT IS STILL
 SHOWN ON THE RISER DIAGRAM.
 B. THE PIPING TO THE KITCHEN SINK WAS CHANGED ON THE
 FLOOR PLAN BUT NOT ON THE RISER DIAGRAM.
 C. THE LAV ARM IN THE TOILET ROOM BY THE WASH MACHINE
 DOES NOT REFLECT THE FLOOR PLAN.
 D. THE 3" WASTE LINE UP DOWNSTREAM OF THE LAST BATHROOM
 SHOWN ON THE FLOOR PLAN IS NOT SHOWN ON THE RISER
 DIAGRAM.
 SECTIONS 106.1.1 & 701.1.
  
 4. SHT P2 GAS RISER DIAGRAM. THE FOLLOWING INFORMATION
 IS REQUIRED ON THE RISER DIAGRAM AND IN THE GAS SYSTEM
 CALCULATIONS:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. -- NOT ALL LENGHTS ARE INDICATED.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED. -- NOT ALL PIPE
 SECTIONS SHOW THE MATERIAL.
  
 C. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). -- FURTHEST DISTANCE IS
 INDICATED AS 94 FEET, BUT ADDING UP ALL SHOWN LENGTH
 MEASUREMENTS IT APPEARS TO BE ABOUT 147 FEET. THIS CAN
 BE VERIFIED WHEN COMMENT 4(A) IS ADDRESSED. WHEN
 SCALING THE PIPING ON SHT P1 (1/4"-FT), IT APPEARS THAT
 SOME LENGTHS FROM THE METER TO THE POOL HEATERS ARE
 INCORRECT. PLEASE RECHECK THE LENGTHS. -- INDICATE THE
 DISTANCE FROM THE 2PSI REGULATOR TO THE FURTHEST FIRE
 PLACE.
  
 D. THE PIPING TO THE POOL HEATERS IS SHOWN AS 2PSI AS
 NO REGULATORS ARE SHOWN AT THE HEATERS. PLEASE CLARIFY
 THE INLET PRESSURE TO THE POOL HEATERS.
  
 E. A SHUT OFF VALVE IS REQUIRED DOWNSTREAM OF THE GAS
 REGULATORS. SECTION 409.4. -- ALSO A UNION IS REQUIRED
 DOWNSTREAM OF THE SHUTOFF VALVE FOR THE GAS REGULATOR
 FOR THE SUPPLY LINE FEEDING THE FIREPLACES/GRILL/DOUBLE
 BURNER.
  
 F. SUBMIT MANUF. SPECIFICATIONS FOR THE GAS PRESSURE
 REGULATORS. PLEASE INDICATE THE MODEL NUMBER OF EACH
 REGULATOR AS SOME REGULATORS ARE FOR INDIVIDUAL
 APPLIANCES AND SOME REGULATORS ARE FOR MULTIPLE
 APPLIANCES. SECTIONS 106.1.2 & 409.1.1. REGULATORS
 SHALL BE LISTED.
  
 G. SHT P1, PLASTIC PIPE SHALL BE INSTALLED OUTSIDE
 UNDERGROUND ONLY. PLASTIC PIPE SHALL NOT BE USED WITHIN
 OR UNDER ANY BUILDING OR SLAB PER SECTION 404.14.1.
 PLEASE INDICATE IF THE PIPING WILL BE UNDER ANY SLAB OR
 PORTION OF THE BUILDING. IF NOT INDICATE WHAT THE POOL
 DECK WILL BE BUILD OUT OF AS WELL AS THE AREA BETWEEN
 THE HOUSE AND THE GARAGE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  