| 2009-02-09 10:25:05 | DENIED |
| | REFERENCE: |
| | FBC-2004 FUEL GAS |
| | |
| | 1. SHT P2 GAS RISER DIAGRAM. THE FOLLOWING INFORMATION |
| | IS REQUIRED ON THE RISER DIAGRAM AND IN THE GAS SYSTEM |
| | CALCULATIONS: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. -- NOT ALL LENGHTS ARE INDICATED. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. -- NOT ALL PIPE |
| | SECTIONS SHOW THE MATERIAL. |
| | |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). -- FURTHEST DISTANCE IS |
| | INDICATED AS 94 FEET, BUT ADDING UP ALL SHOWN LENGTH |
| | MEASUREMENTS IT APPEARS TO BE ABOUT 147 FEET. THIS CAN |
| | BE VERIFIED WHEN COMMENT 4(A) IS ADDRESSED. WHEN |
| | SCALING THE PIPING ON SHT P1 (1/4"-FT), IT APPEARS THAT |
| | SOME LENGTHS FROM THE METER TO THE POOL HEATERS ARE |
| | INCORRECT. PLEASE RECHECK THE LENGTHS. -- INDICATE THE |
| | DISTANCE FROM THE 2PSI REGULATOR TO THE FURTHEST FIRE |
| | PLACE. |
| | |
| | D. THE PIPING TO THE POOL HEATERS IS SHOWN AS 2PSI AS |
| | NO REGULATORS ARE SHOWN AT THE HEATERS. PLEASE CLARIFY |
| | THE INLET PRESSURE TO THE POOL HEATERS. |
| | |
| | E. A SHUT OFF VALVE IS REQUIRED DOWNSTREAM OF THE GAS |
| | REGULATORS. SECTION 409.4. -- ALSO A UNION IS REQUIRED |
| | DOWNSTREAM OF THE SHUTOFF VALVE FOR THE GAS REGULATOR |
| | FOR THE SUPPLY LINE FEEDING THE FIREPLACES/GRILL/DOUBLE |
| | BURNER. |
| | |
| | F. SUBMIT MANUF. SPECIFICATIONS FOR THE GAS PRESSURE |
| | REGULATORS. PLEASE INDICATE THE MODEL NUMBER OF EACH |
| | REGULATOR AS SOME REGULATORS ARE FOR INDIVIDUAL |
| | APPLIANCES AND SOME REGULATORS ARE FOR MULTIPLE |
| | APPLIANCES. SECTIONS 106.1.2 & 409.1.1. REGULATORS |
| | SHALL BE LISTED. |
| | |
| | G. SHT P1, PLASTIC PIPE SHALL BE INSTALLED OUTSIDE |
| | UNDERGROUND ONLY. PLASTIC PIPE SHALL NOT BE USED WITHIN |
| | OR UNDER ANY BUILDING OR SLAB PER SECTION 404.14.1. |
| | PLEASE INDICATE IF THE PIPING WILL BE UNDER ANY SLAB OR |
| | PORTION OF THE BUILDING. IF NOT INDICATE WHAT THE POOL |
| | DECK WILL BE BUILD OUT OF AS WELL AS THE AREA BETWEEN |
| | THE HOUSE AND THE GARAGE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |