| Plan Review Notes For Permit 06020800 |
| Permit Number |
06020800 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2007-07-16 16:41:21 | MECHANICAL REVISION | | | *** DENIED *** | | | 1) REVISED MECHANICAL PLANS NEED TO BE SEALED BY THE | | | ENGINEER J. DAVID PUGA, AS PLANS ON FILE ARE SEALED. | | | PLEASE ALSO ENTER ENGINEERS INFORMATION IN THE TITLE | | | BLOCK. | | | | | | 2) NEED TO SHOW THE CFM'S OF ALL SUPPLY AIR GRILLS (SEE | | | SECOND FLOOR PLAN). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|