Plan Review Notes
Plan Review Notes For Permit 06020800
Permit Number 06020800
Review Stop B
Sequence Number 3
Notes
Date Text
2006-08-25 00:00:00BUILDING REVIEW 3RD CHECKLIST:
 1- A BULDING PERMIT CAN'T BE ISSUED IF
 ENERGY CALCULATIONS HAVE GROSS ERRORS.
 SEE SECTION 13-103.3 FBC 2004.
 ON PREVIOUS CHECKLIST I ASKED ENGINEER
 TO CHECK SEC. 13-601 FBC 2004 FOR PROPER
 WAY OF CALCULATING OVERHANG LENGTH AND
 HEIGHT. ENERGY CALCULATIONS SUBMITTED
 STILL SHOW INCORRECT OVERHANG AND LENGTH
 DIMENSIONS. NEED TO REVISE AS REQUIRED.
  
 NOTE:
 * ENGINEER TO SEE ATTACHED COPY OF THE
 FLORIDA STATUTE 553.80(2)(B)REGARDING
 DESIGN PROFESSIONALS DOCUMENTS AND FINES
 FOR REPETITIVE PLAN REVIEWS.
  
 2- REVISE SURVEY: PROPERTY IS NOT
 LOCATED IN FLOOD ZONE "C". PROPERTY IS
 LOCATED IN FLOOD ZONE "B" AS PER
 COMMUNITY PANEL NO 120229-0015-B AND
 DATED MARCH 1ST, 1979.
  
 3- TRUSS PACKAGE:
 A) TRUSS ENGINEER TO FOLLOW CHAPTER 471
 FLORIDA STATUTES AND FLORIDA
 ADMINISTRATIVE CODE SECTION 61G15-23.002
 WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS. RUBBER STAMP SIGNATURE IS NOT
 ALLOWED.
  
 B) IF ENGINEER DOESN'T WANT TO SIGN AND
 SEAL EACH DRAWING, THEN HE NEEDS TO
 PROVIDE ALL INFORMATION REQUIRED ON SEC.
 61G15-31.003(4)(A)
  
 C) PROVIDE CORRECT MEAN ROOF HEIGHT.
 SEE PLANS.
  
 4- NOTICE OF COMMENCEMENT IS EXPIRED
 AFTER 90 DAYS OF RECORDING IF WORK IS
 NOT STARTED. SEE SECTION 713.13(2) OF
 FLORIDA STATUTES. NEED RE-RECORDED NOC.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712