| 2006-06-15 00:00:00 | BUILDING REVIEW 2ND CHECKLIST |
| | 1- REVISE ENERGY CALCULATIONS: |
| | A) A/C AREA DOESN'T MATCH PLANS. |
| | |
| | B) ENGINEER WHO PREPARED CALCULATIONS |
| | NEED TO PROVIDE ALL HIS INFORMATION AS |
| | REQUIRED BY CHAPTER 471 FLORIDA STATUTE |
| | AND FAC 61G15-23.002. |
| | |
| | C) COMPLETE ALL INFORMATION ON TOP OF |
| | FORM. |
| | |
| | D) CALCULATIONS SHOWING ORIENTATION OF |
| | BUILDING DON'T MATCH PLANS. CALCULATIONS |
| | NEED TO BE DONE FOR WORST CASE SCENARIO |
| | OR ACTUAL BUILDING ORIENTATION. |
| | |
| | E) REVISE OVERHANG LENGHT AND OVERHANG |
| | HEIGHT TO MATCH PLANS. SEE SECTION |
| | 13-601 FBC 2004 FOR PROPER WAY OF |
| | CALCULATING OVERHANG LENGTH AND HEIGHT. |
| | |
| | F) GLASS AREA IS INCORRECT. SEE SECTION |
| | 13-601.2.A.3.3 FBC 2004 FOR PROPER WAY |
| | OF CALCULATING GLASS AREA. |
| | |
| | NOTE: |
| | ENGINEER TO SEE ATTACHED COPY OF FLORIDA |
| | STATUTE 553.80(2)(B) REGARDING DESIGN |
| | PROFESSIONAL DOCUMENTS. |
| | |
| | 2- A) PLANS NEED THE PALM BEACH COUNTY |
| | IMPACT FEE STAMP AND |
| | B) PROVIDE COPY OF IMPACT FEES PAID |
| | RECEIPT. |
| | |
| | 3- DESIGNER OF RECORD TO SPECIFY ROOF |
| | TILE FASTENING AS REQUIRED BY SEC. |
| | 106.1.1.2 CITY AMENDMENTS TO FBC 2004. |
| | RESPONSE SAYING INSTALLATION AS PER |
| | PRODUCT APPROVAL DOENS'T PROVIDE |
| | INFORMATION REQUIRED TO BE SPECIFIED BY |
| | THE DESIGNER. PRODUCT APPROVAL IS ONLY |
| | TO COMPLY WITH DESIGNER SPECS. |
| | |
| | 4- STAIR DETAILS: |
| | A) INTERIOR STAIRS EXCEED THE 24-25 |
| | RATIO REQUIRED BY SEC. R311.5.3.2. |
| | |
| | B) PROVIDE SPECS SHOWING THAT 4" SPHERE |
| | CAN'T PASS THRU. SEC. R12.2. |
| | |
| | C) SHOW HANDRAIL IN EXTERIOR STAIRS. |
| | |
| | 5- PROVIDE COMPLETE SECTIONS/DETAILS AND |
| | SPECS FOR CHIMNEY CONSTRUCTION. DRAWING |
| | SUBMITTED DOESN'T PROVIDE ANY |
| | INFORMATION FOR SIZES AND FASTENING OF |
| | WOOD FRAMING. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | 6- PROVIDE FLORIDA OR LOCAL PRODUCT |
| | APPROVAL FOR: |
| | A) ALL TRUSS AND STRUCTURAL CONNECTORS |
| | SPECIFIED ON PLANS. PRODUCT APPROVALS |
| | SUBMITTED DON'T COVER ALL OF THEM. |
| | |
| | B) PRECAST LINTELS. NOA SUBMITTED IS |
| | EXPIRED. |
| | |
| | C) LARGE FIXED WINDOWS C AND D. PRODUCT |
| | APPROVALS SUBMITTED DON'T COVER THIS |
| | OVERSIZE WINDOWS. |
| | |
| | D) FLAT ROOF SYSTEM. PROVIDE |
| | CALCULATIONS PER RAS 117 AS REQUIRED BY |
| | GENERAL LIMITATION #7 ON LAST PAGE OF |
| | THE NOA. CALCULATIONS MUST BE SIGNED AND |
| | SEALED BY ANY ONE OF THE PROFESSIONALS |
| | LISTED IN LIMITATION #7. |
| | |
| | E) SPECIFY SIZE OF MULLION AND FASTENERS |
| | FOR WINDOWS C AND D. PROVIDE PRODUCT |
| | APPROVAL IF MULLION SIZE IS BIGGER THAN |
| | 1". SEC. 106.1.2 CITY AMENDMENTS TO FBC. |
| | |
| | 7- PROVIDE COMPLETE DETAILS FOR STEEL |
| | COLUMNS. MISSING TOP CONNECTION. SEC. |
| | 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 8- PROVIDE SURVEY FOR PROPOSED LAYOUT. |
| | STILL SUBMITTING OLD LAYOUT. |
| | |
| | 9- OWES $1200.74 FOR UPDATED VALUATION |
| | AND RADON FEES. THIS COULD NOT BE DONE |
| | ON FIRST REVIEW BECAUSE AREA TABULATION |
| | WAS INCORRECT. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712. |