Plan Review Notes
Plan Review Notes For Permit 06020800
Permit Number 06020800
Review Stop B
Sequence Number 2
Notes
Date Text
2006-06-15 00:00:00BUILDING REVIEW 2ND CHECKLIST
 1- REVISE ENERGY CALCULATIONS:
 A) A/C AREA DOESN'T MATCH PLANS.
  
 B) ENGINEER WHO PREPARED CALCULATIONS
 NEED TO PROVIDE ALL HIS INFORMATION AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTE
 AND FAC 61G15-23.002.
  
 C) COMPLETE ALL INFORMATION ON TOP OF
 FORM.
  
 D) CALCULATIONS SHOWING ORIENTATION OF
 BUILDING DON'T MATCH PLANS. CALCULATIONS
 NEED TO BE DONE FOR WORST CASE SCENARIO
 OR ACTUAL BUILDING ORIENTATION.
  
 E) REVISE OVERHANG LENGHT AND OVERHANG
 HEIGHT TO MATCH PLANS. SEE SECTION
 13-601 FBC 2004 FOR PROPER WAY OF
 CALCULATING OVERHANG LENGTH AND HEIGHT.
  
 F) GLASS AREA IS INCORRECT. SEE SECTION
 13-601.2.A.3.3 FBC 2004 FOR PROPER WAY
 OF CALCULATING GLASS AREA.
  
 NOTE:
 ENGINEER TO SEE ATTACHED COPY OF FLORIDA
 STATUTE 553.80(2)(B) REGARDING DESIGN
 PROFESSIONAL DOCUMENTS.
  
 2- A) PLANS NEED THE PALM BEACH COUNTY
 IMPACT FEE STAMP AND
 B) PROVIDE COPY OF IMPACT FEES PAID
 RECEIPT.
  
 3- DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENING AS REQUIRED BY SEC.
 106.1.1.2 CITY AMENDMENTS TO FBC 2004.
 RESPONSE SAYING INSTALLATION AS PER
 PRODUCT APPROVAL DOENS'T PROVIDE
 INFORMATION REQUIRED TO BE SPECIFIED BY
 THE DESIGNER. PRODUCT APPROVAL IS ONLY
 TO COMPLY WITH DESIGNER SPECS.
  
 4- STAIR DETAILS:
 A) INTERIOR STAIRS EXCEED THE 24-25
 RATIO REQUIRED BY SEC. R311.5.3.2.
  
 B) PROVIDE SPECS SHOWING THAT 4" SPHERE
 CAN'T PASS THRU. SEC. R12.2.
  
 C) SHOW HANDRAIL IN EXTERIOR STAIRS.
  
 5- PROVIDE COMPLETE SECTIONS/DETAILS AND
 SPECS FOR CHIMNEY CONSTRUCTION. DRAWING
 SUBMITTED DOESN'T PROVIDE ANY
 INFORMATION FOR SIZES AND FASTENING OF
 WOOD FRAMING. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 6- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL FOR:
 A) ALL TRUSS AND STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS. PRODUCT APPROVALS
 SUBMITTED DON'T COVER ALL OF THEM.
  
 B) PRECAST LINTELS. NOA SUBMITTED IS
 EXPIRED.
  
 C) LARGE FIXED WINDOWS C AND D. PRODUCT
 APPROVALS SUBMITTED DON'T COVER THIS
 OVERSIZE WINDOWS.
  
 D) FLAT ROOF SYSTEM. PROVIDE
 CALCULATIONS PER RAS 117 AS REQUIRED BY
 GENERAL LIMITATION #7 ON LAST PAGE OF
 THE NOA. CALCULATIONS MUST BE SIGNED AND
 SEALED BY ANY ONE OF THE PROFESSIONALS
 LISTED IN LIMITATION #7.
  
 E) SPECIFY SIZE OF MULLION AND FASTENERS
 FOR WINDOWS C AND D. PROVIDE PRODUCT
 APPROVAL IF MULLION SIZE IS BIGGER THAN
 1". SEC. 106.1.2 CITY AMENDMENTS TO FBC.
  
 7- PROVIDE COMPLETE DETAILS FOR STEEL
 COLUMNS. MISSING TOP CONNECTION. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 8- PROVIDE SURVEY FOR PROPOSED LAYOUT.
 STILL SUBMITTING OLD LAYOUT.
  
 9- OWES $1200.74 FOR UPDATED VALUATION
 AND RADON FEES. THIS COULD NOT BE DONE
 ON FIRST REVIEW BECAUSE AREA TABULATION
 WAS INCORRECT.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.