| 2006-03-01 00:00:00 | *** DENIED *** |
| | 1) THE DOOR FROM THE HALL TO THE LAUNDRY |
| | ROOM WILL NEED TO BE LOUVERED, OR THE |
| | RETURN AIR GRILL WILL NEED TO BE LARGER |
| | (A 5 TON SYSTEM REQUIRES ABOUGHT 725 |
| | SQUARE INCHES). |
| | |
| | 2) THE TRANSFER RETURN AIR DUCT (FLEX) |
| | IN MASTER SUITE IS TO SMALL FOR 605 |
| | CFM'S SUPPLY AIR SEE NOTE #3 (A)&(C) |
| | EXCEPT. |
| | |
| | 3)BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | 4) THE MASTER BATHROOM (HIS) NEEDS AN |
| | EXHUST FAN IN THE SINK AREA DUE TO THE |
| | SHOWER, PER 2004 FBC/M 402.3.1 . |
| | |
| | 5) PLEASE CORRECT THE "KW" SIZES ON THE |
| | A/C EQUIPMENT SCHEDULE ON PAGE M3 TO |
| | KILOWATTS. |
| | |
| | 6) PLEASE SHOW THE SENSIBLE COOLING |
| | BTU'S ON THE A/C EQUIPMENT SCHEDULE. |
| | |
| | 7) PLEASE PROVIDE THE MANUFACTURE'S |
| | SPECIFICATION SHEETS SHOWING THE TOTAL, |
| | SENSIBLE, AND LATENT COOLING BTU'S AS |
| | THE LATENT COOLING BTU'S ON THEMANUAL |
| | J APPEAR VERY HIGH. |
| | |
| | 8) PLEASE SHOW THE COPPER LINE SIZES ON |
| | THE A/C EQUIPMENT SCHEDULE. |
| | |
| | 9) BOOSTER FANS ARE NOT PERMITTED IN |
| | DRYER VENTS AS THEY VOID THE DRYER |
| | WARRANTY PLEASE CORRECT. |
| | |
| | 10) PLEASE SUBMITT MANUFACTURE'S SPEC'S |
| | AND INSTALLATION INSTRUCTIONS FOR EACH |
| | GAS FIRE PLACE. |
| | |
| | MECHANICAL PLAN REVIEW BY; |