| Plan Review Notes For Permit 06020800 |
| Permit Number |
06020800 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-03 00:00:00 | DENIED; | | | 1.PIPING UNDER THE SLAB MUST BE | | | REMOVABLE FROM SLEEVED, SLEEVING MUST BE | | | VENTED TO THE OUTSIDE. SLEEVES MUST HAVE | | | A BENDING RADIUS LARGE ENOUGH TO ACEPT | | | THE BENDING RADIUS OF AN APPROVED | | | FLEXABLE PIPE. | | | 2.SHOW COMBUSTION AIR CALCULATIONS FOR | | | WATER HEATER VENTS THRU WALL. | | | 3. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED. | | | 4.SHOW ALL CUT SECTIONS OF PIPE ON GAS | | | RISER. | | | 5.NO PROVISIONS HAVE BEEN MADE FOR | | | FUTURE POOL HEATER, GAS B-B-Q OR | | | GENERATOR. IF ADDED LATER PIPE SIZES | | | WILL CHANGE. | | | 6.PIPE SIZING IS NOT CORRECT. 1 1/4" | | | GALV IS REQUIRED FROM METER TO "TEE" FOR | | | FIREPLACES. | | | GAS PLAN TEVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|