Plan Review Notes
Plan Review Notes For Permit 06020800
Permit Number 06020800
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-01 00:00:00********** UNSAT ***********
  
 1)NOTE: PLEASE SEE ZONING NOTES AS THIS
 WILL AFFECT THE ELECTRICAL PLANS AND
 DESIGN OF REAR BLDG.
  
 2)NOTE: PLEASE SEE FS 471.025 WHICH
 REQUIRES A LEGAL "SIGNATURE" FOR
 ENGINEER, THIS APPEARS TO BE "INITIALS"?
 IF INDEED THIS IS THE LEGAL SIGNATURE ,
 PLEASE PROVIDE A SIGNED,DATED AND SEALED
 LETTER FOR VERIFICATION.
 PLEASE BE SURE LETTER IS PROPERLY
 NOTORIZED UNDER FS 117.05.
 ** PLEASE KNOW, THIS WILL BE PLACED IN
 OUR SIGNATURE FILE FOR ANY FUTURE
 REFERENCE.
  
 3)NOTE: PLEASE HAVE PLANS REFERENCE THE
 CURRENT NFPA-70 IN ADOPTION, WHICH IS
 THE 2002 EDITION.
  
 4)NOTE: PLEASE SEE SMOKE DETECTOR
 REQUIRED PER NFPA-72 11.5.1.1 IS TO BE
 LOCATED AT THE FIRST FLR, IN THE
 IMEDIATE VICINITY OF THE STAIRS LEADING
 TO THE FLOOR ABOVE. A SD SHOWN ON PLANS
 DOES NOT APPEAR TO BE ON FIRST FLR?
 PLEASE ADJUST.
  
 5)NOTE: PLEASE SEE 210.8A6, WHICH
 REQUIRES ALL COUNTERSPACE RECEPTS IN
 KITCHEN AREASTO BE GFI/GFI PROTECTED.
 PLEASE SEE REDLINED PLANS, PENINSULAR.
  
 6)NOTE: PLEASE SEE 210.52D FOR MISSING
 BATH GFI TO BE LOCATED WITHIN 3' OF LAV.
 REDLINED.
  
 7)NOTE: PLEASE SEE 210.11C3 WHICH
 REQUIRESDEDICATED BATH(S) CIRCUIT(S).
 PLEASE SEE THESE CAN NOT SERVE ANY OTHER
 AREAS,A ND MUST BE 20A AND #12 AWG.
 PLEASE ADJUST , AS PANEL SCHEDULES
 INDICATE 15A, #14 ETC.
  
 8)NOTE: PLEASE CORRELATE THE NUMBER OF
 A/C SYSTEMS ON PLANS WITH PANEL
 SCHEDULE.
 PLEASE SEE THREE SYSTEMS ARE SHOWN ON
 PANELS "A" AND "B", HOWEVER ONLY TWO
 SYSTEMS ARE SHOWN ON PLANS. THIS DOES
 NOT INCLUDE THE SYSTEM IN GARAGE /APT.
 ** PLEASE VERIFY IF ONLY TWO SYSTEMS IN
 MAINHOUSE THE HEAT/KW RATINGS OF
 HEATSTRIP. ONE SHOWS 5KW AND THE OTHER
 6KW WHICH SEEMS LOW FOR A HOUSE OF THIS
 SIZE. THIS IS ONLY A NOTE, AND DOES NOT
 APPLY FOR CODE COMPLIANCE.
  
 9)NOTE: PLEASE SEE CIRCUITING AS
 INDICATED ON PLANS AND PANEL SCHEDULES
 AND THE 2002 NEC 210.12B FOR ARC FAULT
 PROTECTION OF ALL "OUTLETS" IN BEDRMS.
 PLEASE KNOW THIS INCLUDES , SD'S
 RECEPTS, LTS, FANS ETC.
 PLEASE ADJUST ALL CIRCUITING ON PANEL
 SCHEDULES OR PLANS.
  
 10)NOTE: PLEASE LABEL ACCORDINGLY TO THE
 LOCATIONS AS NOTED ON PLANS. BEDRMS
 RECEPTS, MASTER BEDRM LTS ETC.
 ** PLEASE KNOW THIS MAY VERY WELL CHANGE
 AS THE WIRING OF STRUCTURE MAY VARY FROM
 ACTUAL PLANS AND REVISIONS CAN BE
 SUBMITTED AT A LATER DATE.215.5
  
 11)NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN THE GENERAL LIGHTING LOADS
 @ 3W/PER SQ FT AS THESE RECESSED LTS GO
 ABOVE THE NORMAL LOADS.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 12)NOTE: PLEASE CORRELATE THE LOADS ON
 PANEL SCHEDULES AND LOAD CALCULATIONS.
 PLEASE SEE SOME LOADS ON PANELS WHICH
 ARE NOT ON LOAD CALCS. PLEASE ALSO CARRY
 THIS ADJUSTED LOAD THROUGH TO MAIN HOUSE
 SERVICE.
 (HEAT PUMP, JOCKEY PUMP.
  
 13)NOTE: PLEASE VERIFY THE SIZE OF THE
 GDO'S MOTORS AS BOTH MOTORS SEEM TO BE
 SHOWN ON THE SAME CIRCUIT?
 PLEASE SEE TABLE TO MOTORS AND MULTIPLE
 MOTORS ON A SINLGE BRANCH CIRCUIT.
 430.148
  
 14)NOTE: PLEAS NOTE AND VERIFY THE
 FOOTER STEEL ATDETACHED BLDG. PLEASE
 SEE 250.32 WHICH REQUIRES AN ATTACHMENT
 AT THE GARAGE LOCATION AND A CONNECTION
 TO ANY(METAL)CWP WHICH MAY NOT
 CONTINOUS FROM MAIN HOUSE.
  
 15)NOTE: PLEASE PROVIDE A MEANS OF
 CONTROLING THE EGRESS LT AT THE GARAGE
 APT FOR OUTSIDE STAIRS. THIS ADDITIONAL
 SWITCH SHOULD BE LOCATED AT THE BOTTOM
 OF THE STAIRS.
 210.70,LS 101 7.8
  
 16)NOTE: PLEASE SEE FAC 61G1-16.004
 WHICH REQUIRES THE ADDRESS/LOCAITON FO
 PROJECT ON PLANS.
 PLEASE SEE THE ADDRESS OF 214 10TH ST AS
 NOTED.
  
 17)NOTE: PLEASE CORRELATE ALL CIRCUITING
 ON PLANS WITH THE SUBMITTED PANEL
 SCHEDULES.
 PLEASE SEE CU-1 CIRCUITS AND ANY OTHER
 AS REDLINED ON PLANS.
  
 18)NOTE: PELASE VERIFY THE DINING RM
 CIRCUITS , AS AN RECEPTS SHALL BE ON ONE
 OR MORE OF THE SMALL APPLIANCE CIRCUITS
 PROVIDED.
 PLEASE SEE 210.52B1, ONE CIRCUIT DOES
 NOT SEEM TO BE ON A SM APPL CIRCUIT.
  
 19)NOTE: PLEASE CORRELATE ALL PANELS
 WITH RISER DIAGRAM. PLEASE SEE PANEL "C"
 AS 225A AND 150A,PANEL "B" AS 150A AND
 200A, ETC.
 PLEASE ADJUST. 215.5
  
 20)NOTE: PLEASE PROVIDE A MCB AT PANEL
 "C" AT GARAGE/ APT BLDG. THIS IS BEING
 CONSIDE DETACHED AS DEFINITIONS SET
 FORTH IN FBC 2004.
 225.31
  
 21)NOTE: PLEASE SEE NOTICE OF
 COMMENCEMENT AS SUBMITTED HAS SINCE
 EXPIRED AND A NEW RE-RRECORDED NOC WILL
 BE REQUIRED BEFORE PICKING UP PERMIT.
 PLEASE SEE FS 713.13(2) WHICH STATES, IF
 WORK HAS NOT COMMENCED WITHIN 90 DAYS OF
 RECORDING SUCH NOC, THE NOC SHALL BECOME
 VOID.
  
 ** PLEASE SEE ANY OTHER POSSIBLE
 COMMENTS FROM OTHER TRADES WHICH MAY
 AFFECT ELECTRICAL PLANS. (ZONING AS
 NOTED ETC).
  
 ** PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS FROM SETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING.
 PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED
 SHEETS FOR REFERENCE.
 PLEASE BE SURE THIS IS DONE AS THIS WILL
 HELP TO ALLEAVIATE ANY DELAYS IN REVIEW
 TIMES AND PROCESSING PROJECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2006-02-28 00:00:00IN ELEC FOR REVIEW.
 NOTES WILL FOLLOW, AS REVIEW IS IN
 PROGRESS.