| 2006-03-01 00:00:00 | ********** UNSAT *********** |
| | |
| | 1)NOTE: PLEASE SEE ZONING NOTES AS THIS |
| | WILL AFFECT THE ELECTRICAL PLANS AND |
| | DESIGN OF REAR BLDG. |
| | |
| | 2)NOTE: PLEASE SEE FS 471.025 WHICH |
| | REQUIRES A LEGAL "SIGNATURE" FOR |
| | ENGINEER, THIS APPEARS TO BE "INITIALS"? |
| | IF INDEED THIS IS THE LEGAL SIGNATURE , |
| | PLEASE PROVIDE A SIGNED,DATED AND SEALED |
| | LETTER FOR VERIFICATION. |
| | PLEASE BE SURE LETTER IS PROPERLY |
| | NOTORIZED UNDER FS 117.05. |
| | ** PLEASE KNOW, THIS WILL BE PLACED IN |
| | OUR SIGNATURE FILE FOR ANY FUTURE |
| | REFERENCE. |
| | |
| | 3)NOTE: PLEASE HAVE PLANS REFERENCE THE |
| | CURRENT NFPA-70 IN ADOPTION, WHICH IS |
| | THE 2002 EDITION. |
| | |
| | 4)NOTE: PLEASE SEE SMOKE DETECTOR |
| | REQUIRED PER NFPA-72 11.5.1.1 IS TO BE |
| | LOCATED AT THE FIRST FLR, IN THE |
| | IMEDIATE VICINITY OF THE STAIRS LEADING |
| | TO THE FLOOR ABOVE. A SD SHOWN ON PLANS |
| | DOES NOT APPEAR TO BE ON FIRST FLR? |
| | PLEASE ADJUST. |
| | |
| | 5)NOTE: PLEASE SEE 210.8A6, WHICH |
| | REQUIRES ALL COUNTERSPACE RECEPTS IN |
| | KITCHEN AREASTO BE GFI/GFI PROTECTED. |
| | PLEASE SEE REDLINED PLANS, PENINSULAR. |
| | |
| | 6)NOTE: PLEASE SEE 210.52D FOR MISSING |
| | BATH GFI TO BE LOCATED WITHIN 3' OF LAV. |
| | REDLINED. |
| | |
| | 7)NOTE: PLEASE SEE 210.11C3 WHICH |
| | REQUIRESDEDICATED BATH(S) CIRCUIT(S). |
| | PLEASE SEE THESE CAN NOT SERVE ANY OTHER |
| | AREAS,A ND MUST BE 20A AND #12 AWG. |
| | PLEASE ADJUST , AS PANEL SCHEDULES |
| | INDICATE 15A, #14 ETC. |
| | |
| | 8)NOTE: PLEASE CORRELATE THE NUMBER OF |
| | A/C SYSTEMS ON PLANS WITH PANEL |
| | SCHEDULE. |
| | PLEASE SEE THREE SYSTEMS ARE SHOWN ON |
| | PANELS "A" AND "B", HOWEVER ONLY TWO |
| | SYSTEMS ARE SHOWN ON PLANS. THIS DOES |
| | NOT INCLUDE THE SYSTEM IN GARAGE /APT. |
| | ** PLEASE VERIFY IF ONLY TWO SYSTEMS IN |
| | MAINHOUSE THE HEAT/KW RATINGS OF |
| | HEATSTRIP. ONE SHOWS 5KW AND THE OTHER |
| | 6KW WHICH SEEMS LOW FOR A HOUSE OF THIS |
| | SIZE. THIS IS ONLY A NOTE, AND DOES NOT |
| | APPLY FOR CODE COMPLIANCE. |
| | |
| | 9)NOTE: PLEASE SEE CIRCUITING AS |
| | INDICATED ON PLANS AND PANEL SCHEDULES |
| | AND THE 2002 NEC 210.12B FOR ARC FAULT |
| | PROTECTION OF ALL "OUTLETS" IN BEDRMS. |
| | PLEASE KNOW THIS INCLUDES , SD'S |
| | RECEPTS, LTS, FANS ETC. |
| | PLEASE ADJUST ALL CIRCUITING ON PANEL |
| | SCHEDULES OR PLANS. |
| | |
| | 10)NOTE: PLEASE LABEL ACCORDINGLY TO THE |
| | LOCATIONS AS NOTED ON PLANS. BEDRMS |
| | RECEPTS, MASTER BEDRM LTS ETC. |
| | ** PLEASE KNOW THIS MAY VERY WELL CHANGE |
| | AS THE WIRING OF STRUCTURE MAY VARY FROM |
| | ACTUAL PLANS AND REVISIONS CAN BE |
| | SUBMITTED AT A LATER DATE.215.5 |
| | |
| | 11)NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN THE GENERAL LIGHTING LOADS |
| | @ 3W/PER SQ FT AS THESE RECESSED LTS GO |
| | ABOVE THE NORMAL LOADS. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | 12)NOTE: PLEASE CORRELATE THE LOADS ON |
| | PANEL SCHEDULES AND LOAD CALCULATIONS. |
| | PLEASE SEE SOME LOADS ON PANELS WHICH |
| | ARE NOT ON LOAD CALCS. PLEASE ALSO CARRY |
| | THIS ADJUSTED LOAD THROUGH TO MAIN HOUSE |
| | SERVICE. |
| | (HEAT PUMP, JOCKEY PUMP. |
| | |
| | 13)NOTE: PLEASE VERIFY THE SIZE OF THE |
| | GDO'S MOTORS AS BOTH MOTORS SEEM TO BE |
| | SHOWN ON THE SAME CIRCUIT? |
| | PLEASE SEE TABLE TO MOTORS AND MULTIPLE |
| | MOTORS ON A SINLGE BRANCH CIRCUIT. |
| | 430.148 |
| | |
| | 14)NOTE: PLEAS NOTE AND VERIFY THE |
| | FOOTER STEEL ATDETACHED BLDG. PLEASE |
| | SEE 250.32 WHICH REQUIRES AN ATTACHMENT |
| | AT THE GARAGE LOCATION AND A CONNECTION |
| | TO ANY(METAL)CWP WHICH MAY NOT |
| | CONTINOUS FROM MAIN HOUSE. |
| | |
| | 15)NOTE: PLEASE PROVIDE A MEANS OF |
| | CONTROLING THE EGRESS LT AT THE GARAGE |
| | APT FOR OUTSIDE STAIRS. THIS ADDITIONAL |
| | SWITCH SHOULD BE LOCATED AT THE BOTTOM |
| | OF THE STAIRS. |
| | 210.70,LS 101 7.8 |
| | |
| | 16)NOTE: PLEASE SEE FAC 61G1-16.004 |
| | WHICH REQUIRES THE ADDRESS/LOCAITON FO |
| | PROJECT ON PLANS. |
| | PLEASE SEE THE ADDRESS OF 214 10TH ST AS |
| | NOTED. |
| | |
| | 17)NOTE: PLEASE CORRELATE ALL CIRCUITING |
| | ON PLANS WITH THE SUBMITTED PANEL |
| | SCHEDULES. |
| | PLEASE SEE CU-1 CIRCUITS AND ANY OTHER |
| | AS REDLINED ON PLANS. |
| | |
| | 18)NOTE: PELASE VERIFY THE DINING RM |
| | CIRCUITS , AS AN RECEPTS SHALL BE ON ONE |
| | OR MORE OF THE SMALL APPLIANCE CIRCUITS |
| | PROVIDED. |
| | PLEASE SEE 210.52B1, ONE CIRCUIT DOES |
| | NOT SEEM TO BE ON A SM APPL CIRCUIT. |
| | |
| | 19)NOTE: PLEASE CORRELATE ALL PANELS |
| | WITH RISER DIAGRAM. PLEASE SEE PANEL "C" |
| | AS 225A AND 150A,PANEL "B" AS 150A AND |
| | 200A, ETC. |
| | PLEASE ADJUST. 215.5 |
| | |
| | 20)NOTE: PLEASE PROVIDE A MCB AT PANEL |
| | "C" AT GARAGE/ APT BLDG. THIS IS BEING |
| | CONSIDE DETACHED AS DEFINITIONS SET |
| | FORTH IN FBC 2004. |
| | 225.31 |
| | |
| | 21)NOTE: PLEASE SEE NOTICE OF |
| | COMMENCEMENT AS SUBMITTED HAS SINCE |
| | EXPIRED AND A NEW RE-RRECORDED NOC WILL |
| | BE REQUIRED BEFORE PICKING UP PERMIT. |
| | PLEASE SEE FS 713.13(2) WHICH STATES, IF |
| | WORK HAS NOT COMMENCED WITHIN 90 DAYS OF |
| | RECORDING SUCH NOC, THE NOC SHALL BECOME |
| | VOID. |
| | |
| | ** PLEASE SEE ANY OTHER POSSIBLE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS. (ZONING AS |
| | NOTED ETC). |
| | |
| | ** PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS FROM SETS AND ONLY |
| | INSERT NEW REVISED SHEETS INTO COMPLETE |
| | SETS FOR REVIEW AND STAMPING. |
| | PLEASE SUBMIT ONE COPY OF ALL OLD/VOIDED |
| | SHEETS FOR REFERENCE. |
| | PLEASE BE SURE THIS IS DONE AS THIS WILL |
| | HELP TO ALLEAVIATE ANY DELAYS IN REVIEW |
| | TIMES AND PROCESSING PROJECT. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| 2006-02-28 00:00:00 | IN ELEC FOR REVIEW. |
| | NOTES WILL FOLLOW, AS REVIEW IS IN |
| | PROGRESS. |