Plan Review Notes
Plan Review Notes For Permit 06020800
Permit Number 06020800
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-20 00:00:00BUILDING REVIEW CHECKLIST;
 1- ONLY TWO SETS OF PLANS AND PRODUCT
 APPROVALS ARE REQUIRED.
  
 2- NOC IS EXPIRED AFTER 90 DAYS IF WORK
 IS NOT COMMENCED. NEED RE-RECORDED ONE.
  
 3- A) BUILDING AREAS SHOWN ON PAGE A-1
 DON'T ADD UP. REVISE AS REQUIRED.
 B) SHOW AREA TABULATION IDENTIFYING
 AREAS SEPARATELY. EG: 1ST FLOOR AREA,
 2ND FLOOR AREA, GUEST COTTAGE, ETC. TO
 PROPERLY VALUATE PROJECT AND AREAS TO BE
 CONSIDERED FOR RADON FEES. SEC. 108.3
 CITY AMENDMENTS TO FBC 2004.
 C) RESUBMIT SHEET WITH IMPACT FEES
 PAID STAMP FOR THE FILE WHEN DRAWING IS
 REVISED.
  
 4- PROVIDE COPY OF IMPACT FEES PAID
 RECEIPT.
  
 5- SPECIFY ROOF TILE FASTENING AS
 REQUIRED BY SECTION 106.1.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 6- A) WINDOWS IN SECOND FLOOR BEDROOMS
 NUMBERED 200 AND 2004 DON'T MEET THE
 REQUIREMENTS FOR EMERGENCY EGRESS. SEC.
 R10 2004 RESIDENTIAL CODE. (TYPICALLY 24
 SH WINDOWS DON'T MEET THE EGRESS
 REQUIREMENTS) REVISE AS REQUIRED TO SHOW
 COMPLIANCE WITH THIS SECTION.
 B) WINDOWS IN LIBRARY ROOM DON'T MEET
 THE EGRESS REQUIREMENTS EITHER, IF ROOF
 USED FOR SLEEPING PURPOSES. IF THIS ROOM
 IS NOT INTENDED FOR SLEEPING, THEN,
 ARCHITECT TO CLEARLY SPECIFY ON PLANS
 THAT ROOM IS NOT TO BE USED FOR SLEEPING
 PURPOSES.
  
 7- PROVIDE COMPLETE SECTION/DETAILS THRU
 INTERIOR STAIRS & EXTERIOR STAIRS. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004 AND
 SEC. R311 2004 RESIDENTIAL CODE.
  
 8- A) SPECIFY ATTIC ACCESS SIZE IN MAIN
 HOUSE. SEC. R807 2004 RESIDENTIAL CODE.
 B) PROVIDE ATTIC ACCESS SIZE AND
 LOCATION IN 2ND FLOOR ABOVE GARAGE.
 SECTION R807 2004 RESIDENTIAL CODE.
 C) PROVIDE ATTIC ACCESS SIZE AND
 LOCATION AT 1ST FLOOR LIBRARY WING AREA.
 SEC. R807 2004 RESIDENTIAL CODE.
  
 9- PROVIDE SMOKE DETECTORS AS REQUIRED
 BY SEC. R313 2004 RESIDENTIAL CODE.
  
 10- SHEET A2.4: A) SPECIFY FIREBLOCKING
 MATERIAL AND LOCATION IN DETAIL 2.
 B) SPECIFY FIREBLOCKING MATERIAL AND
 LOCATION IN CONCEALED SPACES IN ALL
 BUILDING SECTIONS & FIREPLACES/CHIMNEYS.
 SEC. R602.8 2004 RESIDENTIAL CODE.
  
 11- PROVIDE COMPLETE SECTIONS/DETAILS
 AND SPECS FOR CHIMNEYS CONSTRUCTION.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
  
 12- CLARIFY IF ATTIC VENTILATIONIS 4"
 CONTINUOUS OR IT'S SPACED THROUGHOUT
 ROOF. SPECIFY SIZE AND EXACT LOCATION.
 SEC. R806 2004 RESIDENTIAL CODE.
  
 13- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL (GO TO WWW.FLORIDABUILDING.ORG
 TO DOWNLOAD FLORIDA PRODUCT APPROVALS.
 DADE COUNTY NOA'S ALONE ARE NOT
 AUTOMATICALLY STATEWIDE FLORIDA PRODUCT
 APPROVALS) AS REQ'D BY RULE 9B-72 FOR:
 A) FLAT ROOF. AND CLEARLY SPECIFY
 APPROVED ASSEMBLY TO BE INSTALLED TO
 VERIFY COMPLIANCE WITH GENERAL
 LIMITATION #7 OR #9.
 B) ALL TRUSS ANCHORS AND STRUCTURAL
 CONNECTORS SPECIFIED ON PLANS.
 C) ENTRY DOOR.
 D) ROOF TILE.
 E) PRECAST LINTELS.
 F) FRENCH DOORS WITH AND WITHOUT
 SIDELITES. AND CLEARLY IDENTIFY GLASS
 TYPE TO BE USED TO VERIFY COMPLIANCE
 WITH CALCULATED DESIGN PRESSURES.
 ***NOTE: 3 DIFFERENT DADE COUNTY NOA'S
 WERE SUBMITTED. SUBMIT ONLY THE ONE THAT
 IS GOING TO BE INSTALLED.
 G) FIXED WINDOWS.
 H) LARGE FIXED WINDOWS AS SPECIFIED
 FOR WINDOWS MARKED C AND D IN WINDOW
 SCHEDULE. ***NOTE: SEE DADE COUNTY NOA
 FOR MAXIMUM SIZE LIMITATIONS.
 I) SINGLE HUNG WINDOWS.
 J) WINDOW MULLIONS.
 K) GARAGE DOORS. ***NOTE: SEE
 ELEVATIONS FOR TYPE OF DOORS SHOWN.
  
 14- DESIGNER OF RECORD TO REVIEW AND
 APPROVE IN WRITTING (TYP. DONE WITH THE
 STANDARD REVIEW STAMP) ALL PRODUCT
 APPROVALS PRIOR TO SUBMITTAL TO THIS
 OFFICE AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004
  
  
 15- EXTERIOR ELEVATIONS: SHOW HEIGHT OF
 CHIMNEYS TO VERIFY COMPLIANCE WITH
 CLEARANCES SHOWN ON FIGURE R1003.1 OF
 2004 RESIDENTIAL CODE.
  
 16- BALCONY GUARDRAILS TO SHOW
 CLEARANCES TO VERIFY COMPLIANCE WITH
 SEC. R312 2004 RESIDENTIAL CODE.
  
 17-A) PROVIDE SECTION/DETAILS FOR DOORS
 AND WINDOWS STRUCTURAL BUCKS. SEE
 PRODUCT APPROVAL FOR REQUIRED SIZE AND
 SEC. R613.6.2 2004 RESIDENTIAL CODE FOR
 PROPER INSTALLATION.
 B) PROVIDE GARAGE DOOR STRUCTURAL
 BUCK DETAIL. SECTION 106.1.2 OF CITY
 AMENDMENTS TO FBC 2004.
  
 18- SPECIFY CONCRETE SLAB JOINTS OR
 SPECIFY WWM SUPPORTS AS REQUIRED BY SEC.
 R506.2.4 EXCEPTION #2 OF 2004
 RESIDENTIAL CODE.
  
 19- DRAWING S-2: A) SPECIFY SPACING FOR
 2"X4" BLOCKING TO SUPPORT WINDOW IN WOOD
 FRAMED ARCH DETAIL. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 B) REVISE ELEVATION FOR PRECAST
 LINTEL PCL7. SEE PLANS FOR SIZE OF
 GARAGE DOOR.
  
 20- DRAWING S-3: A) LAYOUT SHOWN BY
 STAIRCASE DOESN'T MATCH ARCHITECTURAL
 PLANS. REVISE AS REQUIRED.
 B) DETAIL 03/S3 DOESN'T WORK. SEE
 ARCHITECTURAL PLANS. THERE IS NOT
 CONCRETE BLOCK WALL ON SECOND FLOOR.
 REVISE AS REQUIRED.
 C) CLARIFY WHY SPECIFYING ONLY ONE
 2X8 LEDGER TO SUPPORT 2ND FLOOR TRUSSES,
 WHILE DETAIL 04/S3 SHOWS DOUBLE LEDGER
 TO SUPPORT ROOF JACKS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
 D) FLAT ROOF ABOVE LIBRARY AND GUEST
 ROOM DON'T MATCH ARCHITECTURAL PLANS.
 REVISE AS REQUIRED.
 E) DETAIL 05/S3: HOW ARE ANCHOR BOLTS
 EMBEDED 6". SEE SLAB THICKNESS, COLUMN
 PLATE SIZE AND CB7 SIZE. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
 F) BEAMS SPECIFIED ON SECOND FLOOR
 PLAN DON'T MATCH THOSE SHON ON SECTIONS
 AND DETAILS. EG: SEE SECTION B ON SHEET
 S-5. REVISE ALL BEAMS SHOWN IN FRAMING
 PLANS TO MATCH DETAILS.
 G) PROVIDE SECTION DETAIL THRU
 EXTERIOR WALL ABOVE COVERED PATIO TO
 SHOW INSTALLATION OF PCL6, TB6 AND
 BALCONY CONCRETE SLAB. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 21- PROVIDE COMPLETE WALL SECTION THRU
 INTERIOR METAL STUDS BEARING WALLS. SHOW
 HOW ARE FLOOR TRUSSES SUPPORTED AND
 FASTENED. SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004.
  
 22- MISSING FOOTING FOR STAIRS AT GARAGE
 AREA. SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004.
  
 23- PROVIDE COMPLETE DETAILS FOR STEEL
 COLUMNS. MISSING TOP CONNECTION. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 24- PROVIDE SOIL TEST REPORT.
  
 25- PROVIDE SURVEY FOR PROPOSED LAYOUT.
 OLD LAYOUT SUBMITTED IS NOT GOOD IF
 HOUSE IS DEMOLISHED. MAKE SURE NEW
 SURVEY HAS ORIGINAL SIGNATURE AS
 REQUIRED BY CHAPTER 472 FLORIDA STATUTES
  
 26- ENERGY CALCULATIONS: A) A/C AREA
 DOESN'T MATCH PLANS.
 B) ENGINEER WHO PREPARED ENERGY CALCS
 NEED TO PROVIDE ALL HIS INFORMATION AS
 REQUIRED BY CHAPTER 471 FLORIDA STATUTES
 AND FLORIDA ADMINISTRATIVE CODE.
 C) SPECIFY HOW IS R5 INSULATION
 ACHIEVED FOR CONCRETE SLAB?.
 D) SPECIFY HOW IS R17 INSULATION
 ACHIEVED FOR EXTERIOR CONCRETE BLOCK
 WALLS?
 E) COMPLETE ALL INFORMATION ON TOP OF
 FORM.
 F) OWNER/AGENT TO SIGN AND DATE
 BOTTOM OF FORM.
  
 27- STRUCTURAL DRAWINGS TO HAVE PROJECT
 CORRECT AND COMPLETE ADDRESS AS REQUIRED
 BY CHAPTER 471 FLORIDA STATUTES AND
 FLORIDA ADMINISTRATIVE CODE.
  
 28- PLEASE RETURN REVIEWED SET AFTER ALL
 CORRECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS.
  
 29- DRAWING A3.1: LEGEND DON'T MATCH
 ELEVATIOONS. EG: SEE ITEM #009. CALLS
 FOR IMPACT RESISTANT DOORS. ELEVATION
 SHOWS CHIMNEY. REVISE ALL NOTES AS
 REQUIRED.
  
 30- DRAWING S-6: UPDATE CODES. SEE
 COMMENTS ON PLANS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712