| 2007-09-28 15:19:16 | | | | PERMIT#06020782 | | | 218 ALMERIA ROAD | | | ELECTRICAL PLAN REVIEW | | | WEST PALM BEACH, FL. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE REVISION SUBMITTED FOR SHEET E1.0 HAS OMITTED | | | THE RISER DIAGRAM. PROVIDE A RISER DIAGRAM PER 215.5. | | | NOTE THE GENERATOR AND RELATED EQUIPMENT MUST BE | | | PERMITTED SEPARATELY. | | | | | | 2} THERE IS NOW AN OVEN AND MICROWAVE IN THE KITCHEN | | | THAT WAS NOT ON THE PERMIT SET OF PLANS OR IN THE LOAD | | | CALCS. RECALCULATE THE LOAD ON SHEET E2.0 AND RESUBMIT. | | | INCLUDE ALL ADDED LOADS NOT ON THE PERMIT SET IN ORDER | | | THAT COMPLIANCE WITH ARTICLE 230 CAN BE REVIEWED. | | | | | | 3} THERE IS AN AIR HANDLER IN THE ?NEW STORAGE? ROOM ON | | | SHEET E1.0. CLARIFY IF THIS IS THE AHU THAT WAS | | | UPSTAIRS IN THE PERMITTED SET, OR IF A THIRD SYSTEM HAS | | | BEEN ADDED. IF SO ADD TO CALCS. | | | | | | 4} SHEET E1.0, AN A/C CONDENSER IS SHOWN IN THE STORAGE | | | ROOM. LOCATE IN THE ACTUAL PHYSICAL LOCATION ON THE | | | PLAN. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|