 PERMIT#06020782
 218 ALMERIA ROAD
 ELECTRICAL PLAN REVIEW
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE REVISION SUBMITTED FOR SHEET E1.0 HAS OMITTED
 THE RISER DIAGRAM. PROVIDE A RISER DIAGRAM PER 215.5.
 NOTE THE GENERATOR AND RELATED EQUIPMENT MUST BE
 PERMITTED SEPARATELY.
  
 2} THERE IS NOW AN OVEN AND MICROWAVE IN THE KITCHEN
 THAT WAS NOT ON THE PERMIT SET OF PLANS OR IN THE LOAD
 CALCS. RECALCULATE THE LOAD ON SHEET E2.0 AND RESUBMIT.
 INCLUDE ALL ADDED LOADS NOT ON THE PERMIT SET IN ORDER
 THAT COMPLIANCE WITH ARTICLE 230 CAN BE REVIEWED.
  
 3} THERE IS AN AIR HANDLER IN THE ?NEW STORAGE? ROOM ON
 SHEET E1.0. CLARIFY IF THIS IS THE AHU THAT WAS
 UPSTAIRS IN THE PERMITTED SET, OR IF A THIRD SYSTEM HAS
 BEEN ADDED. IF SO ADD TO CALCS.
  
 4} SHEET E1.0, AN A/C CONDENSER IS SHOWN IN THE STORAGE
 ROOM. LOCATE IN THE ACTUAL PHYSICAL LOCATION ON THE
 PLAN.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  