| Notes |
| Date |
Text |
| 2006-03-03 00:00:00 | *** DENIED *** | | | 1)ENERGY CALCULATIONS NEED TO BE ON FORM | | | 600A-04 (2004) PER FBC 13-600.3.A, AND | | | SIGNED BY OWNER/AGENT. | | | | | | 2) PLESAE PROVIDE COMBUSTION AIR | | | CALCULATIONS FOR GAS CLOTHES DRYER, AND | | | EXISTING GAS WATER HEATER, PER 2004 | | | FBC/M 704.1 . | | | | | | 3) PLEASE CORRECT ON MECHANICAL PLANS | | | PAGE M1.0, FRESH AIR MAKE UP FOR GAS | | | APPLIANCES (WITH BACK DRAFT DAMPER). SEE | | | 2004 FBC/M 707.1 LOUVERS AND GRILLS. | | | | | | 4) PLEASE CORRECT ON MECHANICAL PLANS | | | PAGE M2.0. EXISTING A/C UNIT NEW 30" | | | RETURN AIR GRILL MAY NOT BE INSTALLED IN | | | HER CLOSET AS NO RETURN AIR FROM EXIST | | | HOUSE CAN GET TO IT. PLEASE RELOCATE SO | | | AIR FROM EXISTING HOUSE CAN RETURN TO | | | AHU. | | | | | | 5) PLEASE CORRECT ON MECH. PLANS PAGE | | | M1.0 AIR CONDITIONING SCHEDULE, AND ADD | | | NEW AIR HANDLER AND CONDENSER UNIT MODEL | | | NUMBERS, SEER, TONS, TOTAL BTU'S, | | | SENSIBLE BTU'S, HEATER SIZE (KW), AND | | | COPPER LINE SIZES. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|