Plan Review Notes
Plan Review Notes For Permit 06020782
Permit Number 06020782
Review Stop M
Sequence Number 1
Notes
Date Text
2006-03-03 00:00:00*** DENIED ***
 1)ENERGY CALCULATIONS NEED TO BE ON FORM
 600A-04 (2004) PER FBC 13-600.3.A, AND
 SIGNED BY OWNER/AGENT.
  
 2) PLESAE PROVIDE COMBUSTION AIR
 CALCULATIONS FOR GAS CLOTHES DRYER, AND
 EXISTING GAS WATER HEATER, PER 2004
 FBC/M 704.1 .
  
 3) PLEASE CORRECT ON MECHANICAL PLANS
 PAGE M1.0, FRESH AIR MAKE UP FOR GAS
 APPLIANCES (WITH BACK DRAFT DAMPER). SEE
 2004 FBC/M 707.1 LOUVERS AND GRILLS.
  
 4) PLEASE CORRECT ON MECHANICAL PLANS
 PAGE M2.0. EXISTING A/C UNIT NEW 30"
 RETURN AIR GRILL MAY NOT BE INSTALLED IN
 HER CLOSET AS NO RETURN AIR FROM EXIST
 HOUSE CAN GET TO IT. PLEASE RELOCATE SO
 AIR FROM EXISTING HOUSE CAN RETURN TO
 AHU.
  
 5) PLEASE CORRECT ON MECH. PLANS PAGE
 M1.0 AIR CONDITIONING SCHEDULE, AND ADD
 NEW AIR HANDLER AND CONDENSER UNIT MODEL
 NUMBERS, SEER, TONS, TOTAL BTU'S,
 SENSIBLE BTU'S, HEATER SIZE (KW), AND
 COPPER LINE SIZES.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.