Plan Review Notes
Plan Review Notes For Permit 06020779
Permit Number 06020779
Review Stop Z
Sequence Number 1
Notes
Date Text
2006-03-06 00:00:001) FOUNDATION PLAN DOES NOT MATCH THE
 SITE PLAN APPROVED BY RESOLUTION NO.
 414-05.
  
 A. WEST BUILDING WALL APPEARS TO BE
 SHIFTED 6 FEET TO THE EAST.
 B. CENTER COLUMN UNDER THE PARKING DECK
 EXTENSION APPEARS TO HAVE BEEN REMOVED.
 C. ENTRY TO THE BUILDING HAS BEEN
 SHIFTED 30 FEET TO THE WEST.
  
 2) PROVIDE ELEVATIONS SHOWING HOW THE
 BUILDING WILL LOOK WITH THE CHANGES
 LISTED IN NO. 1 ABOVE, OR REVERT TO THE
 APPROVED PLANS.NEW ELEVATIONS WILL
 REQUIRE AN AMENDMENT TO THE LEASE.
  
 3) NO SURVEY INCLUDED.PROVIDE SURVEY
 SHOWING THE FOUNDATION SETBACKS.
  
 4) PLEASE NOTE THAT THE FOLLOWING
 REQUIREMENT OF RESOLUTION NO. 414-05 HAS
 NOT OCCURRED - THE APPLICANT SHALL
 CONTINUE TO WORK WITH THE CITY?S
 ENGINEERING AND PLANNING DEPARTMENTS TO
 ENSURE THAT THE CIRCULATION AT THE
 ENTRANCE TO THE OFFICE PARKING GARAGE
 AND THE CITYPLACE B GARAGE FUNCTION
 EFFICIENTLY.THIS INCLUDES EXAMINING
 THE POSSIBILITY OF PROVIDING A DEDICATED
 EXIT LANE FOR THE OFFICE PARKING GARAGE.
 A MEETING IS REQUIRED PRIOR TO THE
 APPROVAL OF THE FOUNDATION PERMIT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1435.