| Plan Review Notes For Permit 06020769 |
| Permit Number |
06020769 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-03-16 00:00:00 | **DENIED 2ND TIME** | | | REFERENCE:FBC-2004 R4101 SWIMMING POOLS | | | | | | PLEASE ADJUST YOUR NOTES, DETAILS, OR | | | SUBMITTALS TO REFLECT THE FOLLOWING | | | INFORMATION REQUIRED FOR PLAN REVIEW: | | | | | | 1) PRINT AND SUBMITTAL OF HEAT PUMP NEED | | | TO BE CORRELATED. HEAT PUMP SUBMITTAL | | | INDICATES ELECTRIC AND THE PRINT | | | INDICATES GAS PLEASE CORRELATE. | | | 2) PER SEC. R4101.6.6.5 PLEASE PROVIDE | | | THE MAKE AND MODEL NUMBER OF THE CLEANER | | | FITTING. (ADD TO PRINT, OR SUBMIT | | | DETAIL) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561)805-6730 | | | FAX (561)805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561)805-6721 | | | |
|