| 2006-03-03 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 R4101 SWIMMING POOLS |
| | |
| | PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| | SUBMITTALS TO REFLECT THE FOLLOWING |
| | INFORMATIOM REQUIRED FOR PLAN REVIEW. |
| | |
| | 1) COMPLY WITH FBC-2004 SEC. R4101 |
| | PRIVATE SWIMMING POOLS.(ADD TO NOTES) |
| | 2) FBC-2004 R4101.6.6.3 ENTRAPMENT AD- |
| | VOINANCE PLEASE SUBMIT AN 1-1/2" ATMOS- |
| | PHERIC VENT LENGTH CHART WITH PUMP SIZE |
| | AND TOTAL LENGTH OF VENT TO COMPLY WITH |
| | 3 SECOND RELEASE. |
| | 3) FBC-2004 R4101.6.6.5 WHERE PROVIDED, |
| | THE VACUUM OR PRESSURE CLEANER FITTING |
| | SHALL BE LOCATED AT LEAST 6" AND NOT |
| | GREATER THAN 12" BELOW THE MINIMUM OPER- |
| | ATING WATER LEVEL OR AS AN ATTACHMENT TO |
| | THE SKIMMER.(DETAILS NEEDED) |
| | 4) FBC-2004 R4101.12.1 |
| | PRESSURE TESTS. PER MANUFACTURE |
| | RECOMMENDATIONS, NO AIR TEST SHALL BE |
| | APPROVED FOR PVC PIPE AND FITTINGS. (ADD |
| | TO NOTES) |
| | 5) FBC-2004 4101.14.1 SWIMMING POOL |
| | WATER HEATERS SHALL BEAR THE LABEL OF A |
| | RECOGNIZED TESTING AGENCY. MANUFACTURE |
| | SHEETS REQUIRED. (SUBMITTAL REQUIRED) |
| | 6) FBC-2004 R4101.14.2 WATER RETENTION, |
| | PROVIDE A POSITIVE MEANS OF RETAINING |
| | WATER IN HEATER WHEN PUMP IS SHUT OFF. |
| | (MANUFACTURE CUT SHEETS REQUIRED) |
| | |
| | END OF COMMENTS: |
| | |