| Plan Review Notes For Permit 06020693 |
| Permit Number |
06020693 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-08-02 00:00:00 | *** DENIED *** | | | 1) AS REQUESTED IN LAST TWO REVIEWS, | | | SUPPLY AIR DUCT (FLEX) TO LIVING ROOM | | | NEEDS TO BE SIZED. | | | | | | 2) AS REQUESTED IN LAST TWO REVIEWS, | | | SUPPLY AIR GRILL IN HALL (FOYER) NEEDS | | | TO BE SIZED. | | | | | | 3) SEE ATTACHED NOTICE FS 553.80(2)(B) | | | FOUR TIMES THE FEE. | | | | | | 4) SOME SUPPLY AIR DUCTS ARE SHOWING 2 | | | DIFFERENT SIZES FOR THEM (SEE HIGH | | | LIGHTS ON MECHANICAL PLANS), PLEASE | | | CORRECT. | | | | | | 5) PLEASE EXPLAIN OR REMOVE 18"X30" | | | SUPPLY AIR GRILL UNDER AIR HANDLER. | | | | | | 6) PLEASE SUBMIT MANUAL D CALCULATIONS | | | FOR RESIDENTIAL DUCT DESIGN, PER 2004 | | | FBC/R M1601.1 AND FBC 13-610.1.ABC.1, | | | (AS MOST SUPPLY AIR DUCTS ARE SIZED AT | | | 9") (SEE ATTACHED MANUAL D COVER SHEET). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|