| 2006-08-02 00:00:00 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} NOTE #1 REFERS TO "IAW" PLEASE NOTE |
| | THAT THE STATE OF FLORIDA HAS ADOPTED |
| | NFPA 70 OR THE NEC. IF REFERENCING |
| | ANOTHER CODE TO USE FOR WIRING |
| | COMPLIANCE, INDICATE WHERE IT IS |
| | REFERENCED AS REPLACING THE BUILDING |
| | CODE REFERENCES. ALSO PLEASE INFORM ME |
| | WHERE I CAN OBTAIN OR READ "IAW" CODES. |
| | OTHERWISE TAKE ALLREFERENCES TO SAME OFF |
| | THE DOCUMENTS. |
| | |
| | 2} DUE TO THE METER LOCATION, A |
| | DISCONNECT IS REQUIRED PER 225.32. |
| | INDICATE LOCATION ON PLAN, AND ON THE |
| | RISER. |
| | |
| | 3} CIRCUIT #14 NEEDS #12 WIRE IF A 20 |
| | AMP BREAKER IS USED. 310.16. |
| | |
| | 4} THE PANEL SCHEDULE INDICATES SEPARATE |
| | WASHER AND DRYER, THE PLAN HAS A |
| | COMBINATION UNIT, PLEASE CLARIFY. |
| | |
| | PLEASE SEE THAT THE APPLIANCE OUTLETS IN |
| | THE KITCHEN ARE NOT REQUIRED TO BE GFI, |
| | BUT MUST BE INSTALLED IF ON PLANS. |
| | |
| | 5} RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A) (1) AND 210.52(A)(2). SEE |
| | REVIEWED PLAN. |
| | |
| | 6} BATH ROOMS MUST HAVE RECEPTALES PER |
| | 210.52(D). |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | |
| | |
| | |