| 2006-02-24 00:00:00 | *********** UNSAT ************ |
| | |
| | ** PLEASE KNOW, PLANS ARE NOT COMPLETE |
| | AT THIS TIME. PLEASE ALSO SEE NUMEROUS |
| | ELECTRICAL CODE COMPLIANCE NOTES BELOW. |
| | |
| | |
| | 1)NOTE: PLEASE SUBMIT AN ELECTRICAL |
| | RISER DIAGRAM FOR CODE COMPLIANCE, |
| | SEC'S, AWG'S, GROUNDING ELECTRODE SYSTEM |
| | ETC ETC |
| | 215.5 |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 3) NOTE: PLEASE LIST ALL THE REQ'D |
| | DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| | SCHEDULE. SHALL BE 20A AND #12 AWG. PER |
| | 210.52D, 210.11C3 |
| | |
| | 4)NOTE: PLEASE SEE BATH RMS MISSING THE |
| | REQUIRED GFI RECEPT WITHIN 3' OF LAV'S. |
| | 210.52D, 210.8A |
| | |
| | 5)NOTE: PLEASE SEE MISSING COUNTERSPACE |
| | GFI'S PER 210.52C1 |
| | PLEASE ALSO SEE WHAT APPEARS TO GFI'S |
| | BEHIND THE SINK? IF THESE ARE FOR A DISH |
| | OR DISPOSAL, THEY ARE NOT REQUIED TO BE |
| | GFI AND SHOULD BE NOTED FOR PURPOSE AND |
| | LOCATION. |
| | |
| | 6)NOTE: PLEASE SEE MISSING DISCONNECT |
| | REQUIRED FOR HWH. 422.31 |
| | |
| | 7)NOTE: PLEASE VERIFY PLANS SHOWS |
| | STACKABLE WASHRE/DRYER HOWEVER PANEL |
| | SCHEDULE DOES NOT INDICATE THIS? |
| | 215.5 |
| | |
| | 8)NOTE: PLEASE CORRELATE PANEL SCHEDULE |
| | SIZE. SHOWS 150 AND 200A'S?? |
| | 215.5 |
| | |
| | 9)NOTE: PLEASE SEE MISSING DISCONNECTS |
| | FOR BOTH THE AHU AND CU. 440.11. |
| | PLANS APPEAR TO SHOW RECEPTS FOR EACH?? |
| | PLUG IN TYPE UNITS ARE NOT PERMITTED. |
| | 422.31 ETC |
| | |
| | 10)NOTE: PLEASE LIST "ALL" THE REQUIRED |
| | ARC FAULT PROTECTED CIRCUIT. PLEASE SEE |
| | THE FOLLOWING NOTE. PLEASE ALSO SEE |
| | NOTES ON ELECTRICAL PLANS MENTIONS TO |
| | CIRCUIT THE SD'S TO THE KITCHEN OR BATH |
| | LT CIRCUIT? THIS IS OK, HOWEVER IF THE |
| | SD'S ARE CIRCUITED TO EITHER OFTHESE, |
| | THEN THEY WOULD BE REQUIRED TO BE AFCI |
| | PROTECTED CIRCUITS AND SHOULD ALSO BE |
| | LISTED. |
| | 210.12 |
| | |
| | 11)NOTE: PLEASE SEE PLANS ONLY SEEM TO |
| | INDICATE ONE ARC FAULT CIRCUIT AND THIS |
| | IS ALSO SHOWN AS THE ONLY CIRCUIT FOR |
| | ALL THREE BEDRMS FOR LTS, SD'S FANS, AND |
| | RECEPTS?? PLEASE SEE 240.4,310.16 ETC AS |
| | AS SHOWN THIS ONE CIRCUIT WOULD BE |
| | OVERLOADED. |
| | 215.5 |
| | |
| | 12)NOTE: PLEASE SEE MANY LOCATIONS FOR |
| | MISSING RECEPTS PER 210.52 |
| | |
| | 13)NOTE: PLEASE SEE MISSING EGRESS LTS, |
| | CONTROL ETC PER 210.70, LS 101 7.8 ETC |
| | ALL LOCATIONS ON PLANS. |
| | |
| | 14)NOTE: PLEASE SEE ALL CIRCUITING ON |
| | PANEL SCHEDULE SHOWS ALL CIRCUITS AS |
| | "2-POLE" WHICH INDICATES ALL AS 240V? |
| | PLEASE CORRECT. |
| | 215.5 |
| | |
| | 15)NOTE: PLEASE BE SURE PLANS REFERENCE |
| | THE CURRENT CODE. (2002 NEC ). |
| | |
| | 16)NOTE: PLEASE SEE THE BLDG REVIEW |
| | COMMENTS AS THE VALUE OF $60K IS WAY |
| | LOAW FOR VALUATION OF BUILDING THIS NEW |
| | 3/2. FBC 108.3 |
| | |
| | 17)NOTE: PLEASE SEE PLANS ALSO REFERENCE |
| | THE 2001 FBC, WHEN AS OF OCT 1ST, 2005 |
| | THE STATE OF FLORIDA ADOPTED THE 2004 |
| | FBC. |
| | PLEASE ADJUST PLANS. |
| | |
| | 18)NOTE: PLEASE ALSO SEE BLDG REVIEW |
| | NOTES, AS ONLY PERMIT APPLICATIONS |
| | SUBMIITTED BEFORE JAN 13, 2006 FALL |
| | UNDER THE OLD PALM BEACH COUNTY IMAPCT |
| | FEES, PLEASE KNOW, PLANS WILL BE |
| | REQUIRED TO GO BACK TO PBC TO BE |
| | REVIEWED AND RE-STAMPED AS PLANS WERE |
| | NOT SUBMITTED UNTIL FEB 15, 2006. |
| | |
| | ** PLEASE KNOW, DUE TO THE EXTENT OF |
| | ELECTRICAL COMMENTS, THERE MAY BE |
| | FURTHER COMMENTS ONCE PLANS ARE |
| | COMPLETED. |
| | |
| | ** PLEASE REMOVE ALL OLD/VOIDED SHEETS |
| | AND ONLY INSERT NEW REVISED SHEETS INTO |
| | COMPLETE SETS FOR REVIEW AND STAMPING. |
| | ONE SET OF OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED FOR REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |