| 2006-02-21 00:00:00 | ******** UNSAT ************ |
| | |
| | |
| | 1)NOTE: PLEASE SEE PLANS REFERENCE THE |
| | 2001 FBC AND 2001 SBC. |
| | PLEASE KNOW, THE SBC WENT OUT OF USE TEO |
| | CODE CYCLES AGO. PLEASE ALSO KNOW, AS OF |
| | OCT 1ST, 2005 THE NEW FBC IS 2004 |
| | PLEASE ALSO SEE PLANS INDICATE"PALM |
| | BEACH COUNTY" WHERE THE JOB IS LOCATED |
| | IN THE CITY OF WEST PALM BEACH. |
| | |
| | 2)NOTE: PLEASE SEE MISSING KITCHEN GFI'S |
| | PER 210.52C1 |
| | |
| | 3)NOTE: PLEASE SEE MISSING KITCHEN |
| | PENINSULAR GFI PER 210.52C3 |
| | |
| | 4)NOTE: PLEASE SEE MISSING DEDICATED |
| | BATH CIRCUITS PER 210.52D,210.11C3, MUST |
| | BE 20A AND #12 MIN. |
| | |
| | 5)NOTE: PLEASE SEE MISSING AIC RATING |
| | FOR MAINS AND AND SERVICE EQUIPMENT. |
| | 110.9,215.5 |
| | |
| | 6)NOTE: PLEASE SEE 424.3B FOR OCP FOR |
| | AHU HEAT. PLEASE ALSO VERIFY THE SIZE OF |
| | THE HEAT FOR THIS SIZE OF A DWELLING |
| | UNIT. 5KW SEEMS LOW. |
| | PLEASE SEE 50A OCP IS HIGH FOR 5KW . |
| | |
| | 7)NOTE: PLEASE SEE NUMEROUS 15A CIRCUITS |
| | ON PANEL SCHEDULE WHICH EXCEED THE |
| | BRANCH CIRCUIT RATING. PLEASE SEE 1440 |
| | VA PER 15A CIRCUITS, 1920VA FOR 20A |
| | BRANCH CIRCUITS. |
| | 240.4,310.16,ETC. |
| | |
| | 8)NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | WITH RESPECT TO THE CONSTRUCTION |
| | VALUATION. PER 108.3 FBC ADMINISTRATIVE |
| | SECTION ADOPTED INTO THE LOCAL |
| | AMENDMENTS. |
| | |
| | ** PLEASEBE SURE TO REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO TWO COMPLETE SETS |
| | FOR REVIEW AND STAMPING. |
| | ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE CALL. |
| | |