| Plan Review Notes For Permit 06020655 |
| Permit Number |
06020655 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-24 00:00:00 | DENIED | | | REFERENCE: FBC-2004 424.2 SWIMMING POOLS | | | | | | PLEASE ADJUST YOUR NOTES, DETAILS, OR | | | SUBMITTALS TO REFLECT THE FOLLOWING | | | INFORMATION REQUIRED FOR PLAN REVIEW: | | | | | | 1) PERMIT APPLICATION INDICATES HEATER, | | | BUT THERE IS NONE INDICATED ON THE | | | PRINT.PLEASE CORRELATE. IF A POOL HEATER | | | IS INSTALLED PLEASE PROVIDE THE | | | FOLLOWING INFORMATION ON RESUBMITTAL. | | | 2) FBC-2004 424.2.14.1 SWIMMING POOL | | | WATER HEATERS SHALL BEAR THE LABEL OF A | | | RECOGNIZED TESTING AGENCY.(REQUIRE | | | MANUFACTURE CUT SHEETS SUBMITTAL) | | | 3) FBC-2004 424.2.14.2 WATER RETENTION, | | | PROVIDE A POSITIVE MEANS OF RETAINING | | | WATER IN THE HEATER WHEN PUMP IS SHUT | | | OFF.( REQUIRE MANUFACTURE CUT SHEETS | | | SUBMITTAL) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561)805-6730 | | | FAX(561)805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561)805-6721 |
|