2006-08-17 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE ARE NOW LOADS ON PANEL "B",
 PLEASE SUBMIT SCHEDULE AND CALCULATION
 FOR SAME.
  
 2} THERE IS A SYMBOL TO THE RIGHT OF
 CKTS A14,16 & A18,20 THAT DOES NOT
 APPEAR ON THE LEGEND, BUT CONTAINS A 30
 AMP 3 WIRE,50 AMP 3 WIRE, 30 AMP 4 WIRE
 AND 50 AMP 4 WIRE CIRCUITS. PLEASE
 IDENTIFY PANEL AND CIRCUIT NUMBERS FOR
 THOSE CIRCUITS, THERE ARE NO 3 POLE 30
 AMP CIRCUITS IN THE PANELS SCHEDULES.
  
 3} CIRCUITS A4,16 AND A18,20 ARE
 SPECIFIED AT 220 VOLTS, THE SYSTEM IS
 120/208, WHAT IS THE SOURCE FOR 220 VOLT
 RECEPTACLES?
  
 4} CIRCUITS A 27,29,30,31,32,33 ARE
 SHOWN AS NO LOAD SPARES IN PANEL"A", BUT
 NOW SHOW AS RECEPTACLES ON THE PLAN.
 THEY ARE ALSO SHOWN AS EXISTING, BUT
 DID NOT APPEAR ON THE OIGINAL PLANS.
 PLEASE CLARIFY NEW OR EXISTING, ADD TO
 PANEL SCHEDULE, AND RECALCULATE THE LOAD
 PER 220.
  
 5} PLEASE INDICATE THE ADDED TRACK
 LIGHTING CIRCUIT(S) NUMBERS AND PANEL
 DESIGNATION, CALCULATE PER 220.12(B).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW