| 2006-08-17 00:00:00 | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THERE ARE NOW LOADS ON PANEL "B", |
| | PLEASE SUBMIT SCHEDULE AND CALCULATION |
| | FOR SAME. |
| | |
| | 2} THERE IS A SYMBOL TO THE RIGHT OF |
| | CKTS A14,16 & A18,20 THAT DOES NOT |
| | APPEAR ON THE LEGEND, BUT CONTAINS A 30 |
| | AMP 3 WIRE,50 AMP 3 WIRE, 30 AMP 4 WIRE |
| | AND 50 AMP 4 WIRE CIRCUITS. PLEASE |
| | IDENTIFY PANEL AND CIRCUIT NUMBERS FOR |
| | THOSE CIRCUITS, THERE ARE NO 3 POLE 30 |
| | AMP CIRCUITS IN THE PANELS SCHEDULES. |
| | |
| | 3} CIRCUITS A4,16 AND A18,20 ARE |
| | SPECIFIED AT 220 VOLTS, THE SYSTEM IS |
| | 120/208, WHAT IS THE SOURCE FOR 220 VOLT |
| | RECEPTACLES? |
| | |
| | 4} CIRCUITS A 27,29,30,31,32,33 ARE |
| | SHOWN AS NO LOAD SPARES IN PANEL"A", BUT |
| | NOW SHOW AS RECEPTACLES ON THE PLAN. |
| | THEY ARE ALSO SHOWN AS EXISTING, BUT |
| | DID NOT APPEAR ON THE OIGINAL PLANS. |
| | PLEASE CLARIFY NEW OR EXISTING, ADD TO |
| | PANEL SCHEDULE, AND RECALCULATE THE LOAD |
| | PER 220. |
| | |
| | 5} PLEASE INDICATE THE ADDED TRACK |
| | LIGHTING CIRCUIT(S) NUMBERS AND PANEL |
| | DESIGNATION, CALCULATE PER 220.12(B). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |
| | |
| | |
| | |
| | |