Plan Review Notes
Plan Review Notes For Permit 06020651
Permit Number 06020651
Review Stop E
Sequence Number 1
Notes
Date Text
2006-03-20 00:00:00************ UNSAT ***************
  
 1)NOTE: PLEASE SEE PLANS ARE REQUIRED TO
 BE SIGNED, DATED AND SEALED BY THE
 ENGINEER OF RECORD, (CHANE ENGINEERING)
 FS 471.025
  
 2)NOTE: PLEASE COMPLETE CIRCUITING ON
 PLANS FOR NEW LIGHTING AND CORRELATE
 WITH THE SUBMITTED PANEL SCHEDULE.
 PLEASE CIRCUIT NEW EXIT/EM LTS TO LOCAL
 CIRCUIT. IT WAS NOTED THAT A NOTE IS
 SHOWN ON PLANS TO CONNECT TO LOCAL AREA
 LTS, HOWEVER THE CIRCUITS SHOULD BE
 SHOWN FOR THESE.700.12E
  
 3) NOTE: PLEASE CLARIFY IF THERE ARE NEW
 OR EXISTING SHOW WINDOW RECEPTS.?
 210.62, 220.12
 THESE WILL BE REQUIRED IF NOT EXISITNG.
  
 ** PLEASE SEE IF THERE ARE ANY COMMENTS
 FROM OTHER TRADES WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 ** PLEASE REMOVE ALL OLD/VOIDED SHEETS
 AND ONLY INSERT NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS ARE REQUIRED TO BE
 SUBMITTED BACK FOR REFERENCE. THESE
 SHEETS SHOULD BE SEPARATE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]