| Plan Review Notes For Permit 06020636 |
| Permit Number |
06020636 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-07 00:00:00 | ******DENIED****** | | | | | | 1) PERMIT APPLICATION MENTIONS (12) CARD | | | READERS, HOWEVER PLANS ONLY SHOW (11). | | | | | | 2) IT IS UNDERSTOOD THAT ACCESS CONTROL | | | SYSTEM WILL BE TIED INTO FIRE ALARM. | | | WILL THERE BE AN IMPACT ON EGRESSING THE | | | BUILDING UNDER NORMAL NON-EMERGENCY | | | CONDITIONS? | | | | | | 3) ALL WORK TO COMPLY WITH NFPA 101, | | | 2003 EDITION SECTIONS 7.2.1.5 AND | | | 7.2.1.6 WHERE APPLICABLE. | | | | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | | FIRE PLANS REVIEW (561) 805-6722 |
|