| Plan Review Notes For Permit 06020589 |
| Permit Number |
06020589 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-27 00:00:00 | DENIED; | | | 1. SEE ELECTRICAL NOTE #1. | | | 2.BATHROOM # 1 SHOWER NOT VENTED. | | | 3.ONLY ONE WASHER SHOWN ON FLOOR PLANS 2 | | | SHOWN ON RISER DIAGRAM. | | | 4.WATER HAMMER ARRESTORS REQUIRED ON | | | KITCHEN WATER SUPPLY LINES. | | | 5.CODE TO USE IS FBC-2004 PLUMBING NOT | | | 2001. | | | 6.DELETE NOTE 26. NO CROSS CONNECTIONS | | | PERMITED IN THE POTABLE WATER SUPPLY. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|