Plan Review Notes
Plan Review Notes For Permit 06020587
Permit Number 06020587
Review Stop E
Sequence Number 1
Notes
Date Text
2006-02-23 00:00:00 
 FAILED
  
  
 PROVIDE A DISCONNECTING MEANS PER 600.6
 600.6 DISCONNECTS.
 EACH SIGN AND OUTLINE LIGHTING SYSTEM,
 OR FEEDER CIRCUIT OR BRANCH CIRCUIT
 SUPPLYING A SIGN OR OUTLINE LIGHTING
 SYSTEM, SHALL BE CONTROLLED BY AN
 EXTERNALLY OPERABLE SWITCH OR CIRCUIT
 BREAKER THAT WILL OPEN ALL UNGROUNDED
 CONDUCTORS. SIGNS AND OUTLINE LIGHTING
 SYSTEMS LOCATED WITHIN FOUNTAINS SHALL
 HAVE THE DISCONNECT LOCATED IN
 ACCORDANCE WITH 680.12.
 (1) WITHIN SIGHT OF THE SIGN. THE
 DISCONNECTING MEANS SHALL BE WITHIN
 SIGHT OF THE SIGN OR OUTLINE LIGHTING
 SYSTEM THAT IT CONTROLS. WHERE THE
 DISCONNECTING MEANS IS OUT OF THE LINE
 OF SIGHT FROM ANY SECTION THAT MAY BE
 ENERGIZED, THE DISCONNECTING MEANS SHALL
 BE CAPABLE OF BEING LOCKED IN THE OPEN
 POSITION.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW