| Plan Review Notes For Permit 06020587 |
| Permit Number |
06020587 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-23 00:00:00 | | | | FAILED | | | | | | | | | PROVIDE A DISCONNECTING MEANS PER 600.6 | | | 600.6 DISCONNECTS. | | | EACH SIGN AND OUTLINE LIGHTING SYSTEM, | | | OR FEEDER CIRCUIT OR BRANCH CIRCUIT | | | SUPPLYING A SIGN OR OUTLINE LIGHTING | | | SYSTEM, SHALL BE CONTROLLED BY AN | | | EXTERNALLY OPERABLE SWITCH OR CIRCUIT | | | BREAKER THAT WILL OPEN ALL UNGROUNDED | | | CONDUCTORS. SIGNS AND OUTLINE LIGHTING | | | SYSTEMS LOCATED WITHIN FOUNTAINS SHALL | | | HAVE THE DISCONNECT LOCATED IN | | | ACCORDANCE WITH 680.12. | | | (1) WITHIN SIGHT OF THE SIGN. THE | | | DISCONNECTING MEANS SHALL BE WITHIN | | | SIGHT OF THE SIGN OR OUTLINE LIGHTING | | | SYSTEM THAT IT CONTROLS. WHERE THE | | | DISCONNECTING MEANS IS OUT OF THE LINE | | | OF SIGHT FROM ANY SECTION THAT MAY BE | | | ENERGIZED, THE DISCONNECTING MEANS SHALL | | | BE CAPABLE OF BEING LOCKED IN THE OPEN | | | POSITION. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | |
|