| Plan Review Notes For Permit 06020582 |
| Permit Number |
06020582 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-02-23 00:00:00 | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SHOW THE DISCONNECTING MEANS | | | PER 225.31 AND 225.32 AND GROUNDING PER | | | 250.32. SHOW THE DISCONNECT/PANEL | | | LOCATION ON THE PLAN FOR THE GUEST | | | HOUSE. | | | | | | 2} THE LOAD CALCULATIONS DO NOT REFLECT | | | ITEMS IN THE GUEST HOUSE. SMALL | | | APPLIANCE CIRCUITS (2 MIN.) PER | | | 220.16(A), THERE IS NO CALC FOR ANY OVEN | | | IN EITHER UNIT BUT ONE SHOWN IN THE | | | GUEST HOUSE. NO DISPOSALS IN CALC, ONE | | | SHOWN IN GUEST HOUSE. PLEASE VERIFY | | | EXISTING ITEMS AT NAMEPLATE PER 220.30, | | | AND RESUBMIT. | | | | | | 3} PLEASE PROVIDE A PANEL SCHEDULE FOR | | | THE GUEST HOUSE PANEL SO THAT BRANCH | | | CIRCUIT COMPLIANCE PER ARTICLE 210 CEN | | | BE REVIEWED. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 | | | | | | | | | |
|