| Plan Review Notes For Permit 06020557 |
| Permit Number |
06020557 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2006-03-23 00:00:00 | 1) THE APPROVED ASSEMBLY SELECTED FROM | | | THE NOA IS FOR A WOOD INSULATED ASSEMBLY | | | WITH A -60PSF. THE ENGINEER LETTER | | | REFERS ONLY TO THE ENHANCEMENTOF THE | | | BASE SHEET. WHAT ABOUT THE ENHANCEMENT | | | FOR THE INSULATION? | | | | | | 2) NOTE: THE INFORMATION OR LETTER FROM | | | THE ENGINEER IS A STATEMENT AND NOT THE | | | CALCULATIONS .GENERAL LIMITATION | | | CLEARLY STATED THAT CALCULATIONS SHALL | | | BE PREPARED BY A FLORIDA REGISTERDE | | | PROFESSIONAL FOR THE ENHANCED UPLIFT | | | PRESSURES. SO, SUBMIT THE CALCULATIONS | | | FOR THE ENHANCED UPLIFT PRESSURES OF THE | | | BASE SHEET AND THE INSULATION WHICH WILL | | | MEET THE REQUIRED PRESSURE FOR THIS | | | PROJECT. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | TEL:(561)805-6726 | | | |
|