2006-04-06 00:00:00DENIED;
 1.BREAK SINK; PAGE A-3.1 MUST COMPLY
 WITH FBC-2004 CHAPTER 11 SEC11-4.24.3
 KNEE CLEARANCE 30", WIDE 27", AND 19"
 DEEP FOR FRONTAL APPROACH. 11-4.24.4
 MAXIMUM DEPTH OF SINK IS 6 1/2" ADD
 NOTE. 11-4.24.6 INSULATE PIPES UNDER
 SINK, AND NOTE. 11-4.24.7 FAUCET TO BE
 LEVER, PUSH OR ELECTROIC, SHOW ON PLANS.
 2.PLEASE SHOW TURING RADIUS IN BOTH
 BATHROOMS AND IN H/C STALLS.
 3.URINAL: PAGE A-3.1 SEC.11-4.18.2 MAX.
 17" HIGH TO RIM TO FLOOR. 11-4.18.4
 FLUSH CONTROL NO HIGHER THAN 44". SHOW
 ON DRAWING.
 4.SANITARY RISER DIAGRAM W/C NOT VENTED
 ONLY 12 FIXTURE UNITS PERMITED ON A 3"
 WET VENT FBC-2004 PLUMBING TABLE
 909.3.SAME BRANCH DRAIN, RELIEF VENT
 PART OF THE CIRCUIT VENT SHOULD BE
 BETWEEN THE W/C AND F/D, SEC. 911.4.1.
 (ONE SET OF PLANS RED LINED)
 5.MOP SINK AND FLOOR DRAINS IN KITCHEN
 AREA ARE REQUIRED TO GO TO GREASY WASTE.
 6.UNDER COUNTER GREASE INTERCEPTERS IN
 FOOD PREP AREA ARE NOT PERMITED, (HEALTH
 DEPARMENT) PLEASE CONTACT THE UTILITY
 DEPARTMENT FOR GREASE TRAP SIZING TO
 COMPLY WITH WASTE ORD. 3434. LYNN MASSON
 PHONE NUMBER (561) 822-2271.
 7.TABLE 403.1, REQUIRES 3 DRINKING
 FOUINTAINS ON ONE SHOWN ON RISER
 DIAGRAMS. SEE SEC.410.1 ONLY ONE CAN BE
 BOTTLED WATER.
 8.CLEANOUTS REQUIRED AT THE JUNCTION OF
 THE BUILDING DRAIN AND BUILDING SEWER,
 AND BOTH SIDES OF LIFT STATION,
 SEC708.3.5.
 9.PROVIDE A DETAIL OF THE SEWAGE PUMP OR
 EJECTOT TO BE USED AND LOCATION OF VENT.
 SUMP PUMPS ARE NOT MADE FOR DISCHARGE OF
 SOLID WASTE FROM TOILETS.
 10. CAFE EQUIPMENT NOT LISTED PLEASE
 SHOW IN DETAIL INCLUDE LOCATION OF HAND
 SINKS THAT ARE REQUIRED.
 11.INDIRECT WASTE RECEPTORS SHALL COMPLY
 WITH 802.3 WITH REMOVABLE STRAINERS
 SEC802.3. (FLOOR SINKS)
 12.PAGE P-3.1 WATER HEATER DETAIL SHOW
 THERMAL EXPANSION CONTROL PER. 607.3
 ALSO SHOW LOCATION ON FLOOR PLAN.
 13.CAFE AREA TO BE REVIEWED AND APPROVED
 BY THE DEPARTMENT OF HOTEL AND
 RESTAUANTS. MUST BE APPROVED BEFORE NEXT
 PLUMBING REVIEW. (CONTACT CENTER
 (850)487-1395.