Plan Review Notes
Plan Review Notes For Permit 06020507
Permit Number 06020507
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-03-22 00:00:00******DENIED******
  
 1) NFPA 101, 2003 EDITION SHALL BE
 REFERENCED. SHT A-5.1.
  
 2) CONSTRUCTION, ALTERATION AND
 DEMOLITION SHALL COMPLY WITH NFPA 241.
  
 3) COMPLIANCE WITH FLORIDA FIRE
 PREVENTION CODE, 2004 EDITION. SHT A5.1.
  
 4) PANIC HARDWARE IS REQUIRED ON EXIT
 DOORS SERVING AN OCCUPANT LOAD GREATER
 THAN 100. PLEASE INDICATE ON DOOR
 SCHEDULE.
  
 5) AN ADDRESS IS REQUIRED ON THE
 BUILDING AND SHALL BE A MINIMUM OF 6" IN
 HEIGHT AND CONTRASTING WITH THE
 BACKGROUND.
  
 6) SEPARATE SHOP DRAWING AND PERMITS ARE
 REQUIRED FOR FIRE SPRINKLER AND FIRE
 ALARM SYSTEMS OR REMODEL.
  
 7) THE FIRE DEPARTMENT CONNECTION SHALL
 BE LOCATED NOT FURTHER THAN 150' FROM A
 FIRE HYDRANT. THE DISTANCE EXCEEDS THIS
 REQUIREMENT ON SHT FP-1. PLEASE INDICATE
 IF THERE IS A CLOSER FIRE HYDRANT.
  
 8) FIRE ALARM SYSTEM TO BE UL CERTIFIED
 FOR CENTRAL STATION SERVICE.
  
 9) FIRE ALARM SYSTEM TO BE CLASS A,
 STYLE D OR FULLY ADDRESSABLE.
  
 10) DUCT SMOKE DETECTORS, IN ADDITION TO
 FAN SHUT DOWN, SHALL INITIATE A FIRE
 ALARM WHEN ACTIVATED IN ACCORDANCE WITH
 LOCAL REQUIREMENTS.
  
 11) INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILINGS SHALL COMPLY WITH
 NFPA 101, SECTION 36.3.3.1, AND SHALL BE
 CLASS A OR B. SHT A-0.1.
  
 12) EXIT ACCESS SHALL MEET THE
 REQUIREMENT OF NFPA 101, SECTION
 36.2.5.11.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  