| 2006-03-22 00:00:00 | ******DENIED****** |
| | |
| | 1) NFPA 101, 2003 EDITION SHALL BE |
| | REFERENCED. SHT A-5.1. |
| | |
| | 2) CONSTRUCTION, ALTERATION AND |
| | DEMOLITION SHALL COMPLY WITH NFPA 241. |
| | |
| | 3) COMPLIANCE WITH FLORIDA FIRE |
| | PREVENTION CODE, 2004 EDITION. SHT A5.1. |
| | |
| | 4) PANIC HARDWARE IS REQUIRED ON EXIT |
| | DOORS SERVING AN OCCUPANT LOAD GREATER |
| | THAN 100. PLEASE INDICATE ON DOOR |
| | SCHEDULE. |
| | |
| | 5) AN ADDRESS IS REQUIRED ON THE |
| | BUILDING AND SHALL BE A MINIMUM OF 6" IN |
| | HEIGHT AND CONTRASTING WITH THE |
| | BACKGROUND. |
| | |
| | 6) SEPARATE SHOP DRAWING AND PERMITS ARE |
| | REQUIRED FOR FIRE SPRINKLER AND FIRE |
| | ALARM SYSTEMS OR REMODEL. |
| | |
| | 7) THE FIRE DEPARTMENT CONNECTION SHALL |
| | BE LOCATED NOT FURTHER THAN 150' FROM A |
| | FIRE HYDRANT. THE DISTANCE EXCEEDS THIS |
| | REQUIREMENT ON SHT FP-1. PLEASE INDICATE |
| | IF THERE IS A CLOSER FIRE HYDRANT. |
| | |
| | 8) FIRE ALARM SYSTEM TO BE UL CERTIFIED |
| | FOR CENTRAL STATION SERVICE. |
| | |
| | 9) FIRE ALARM SYSTEM TO BE CLASS A, |
| | STYLE D OR FULLY ADDRESSABLE. |
| | |
| | 10) DUCT SMOKE DETECTORS, IN ADDITION TO |
| | FAN SHUT DOWN, SHALL INITIATE A FIRE |
| | ALARM WHEN ACTIVATED IN ACCORDANCE WITH |
| | LOCAL REQUIREMENTS. |
| | |
| | 11) INTERIOR FINISH CLASSIFICATION FOR |
| | WALLS AND CEILINGS SHALL COMPLY WITH |
| | NFPA 101, SECTION 36.3.3.1, AND SHALL BE |
| | CLASS A OR B. SHT A-0.1. |
| | |
| | 12) EXIT ACCESS SHALL MEET THE |
| | REQUIREMENT OF NFPA 101, SECTION |
| | 36.2.5.11. |
| | |
| | |
| | MIKE WENNERGREN, CAPTAIN/WPBFR |
| | FIRE PLAN REVIEW (561) 805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |