| Date |
Text |
| 2006-03-21 00:00:00 | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE SHEET A.0.1 WHICH |
| | REFERENCES THE FLORIDA FIRE PREVENTION |
| | CODE FOR THE ELECTRICAL CODE?? |
| | PLEASE MAKE THE FOLLOWING REFERENCES FOR |
| | CODES ON ARCHITECTURAL SHEETS AND |
| | ELECTRICAL SHEETS. |
| | 2002. NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR |
| | KITCHENS IN OTHER THAN DWELLINGS UNITS |
| | FOR GFI PROTECTION. |
| | |
| | 3) NOTE: PLEASE CLARIFY SOME FIXTURES |
| | IE: PLEASE SEE F1 WHICH MENTIONS THIS TO |
| | BE A PENDANT TYPE OF FIXTURE, HOWEVER |
| | PLANS INDICATE THESE AS2X4 LAYIN'S?? |
| | |
| | 4) NOTE: PLEASE PROVIDE MANUFEACTURES |
| | SPECS/CUT SHEETS ON LIGHTING CONTROL |
| | PANEL/ENERGY MANAGEMENT SYSTEM. PLEASE |
| | ALSO SUBMIT FOR EM INVERTER PANEL. |
| | 215.5 |
| | PLEASE BE SURE THESE INDICATE THE |
| | LISTING FROM A NRTL. |
| | |
| | 5)NOTE; PLEASE PROVIDE SPECS/ CUT |
| | SHEETS FOR "KIRK KEY INTERLOCK" PLEASE |
| | PROVIDE INFORMATION THAT THE MAIN |
| | BREAKER STILL CONTAINS A MANUAL MEANS OF |
| | DISCONNECT LOCATED ON THE OUTSIDE OF THE |
| | EQUIPMENT. 230.76.230.79 |
| | |
| | 6)NOTE: PLEASE CALRIFY GROUND FAULT |
| | PROTECTION BEING INDICATED FOR BOTH |
| | MAINS. PLEASE SEE 230.95,240.13 ETC AS |
| | GF PROTECTION IS NOT REQUIRED, HOWEVER |
| | MAY BE INSTALLED. |
| | THIS IS ONLY A NOTE AND NO CHANGES ARE |
| | NEEDED. IF PLANS SHOWS THIS, THEN THEY |
| | WILL BE REQUIRED TO BE INSTALLED. |
| | |
| | 7) NOTE: PLEASE SEE FBC CHAPTER 13, |
| | 13-413.1ABC.1, PLEASE SHOW WORST CASE |
| | SCENARIO FOR VOLTAGE DROP. |
| | PLEASE PROVIDE INFORMATION ON ROOMS |
| | WHICH ARE CONSIDERED SEPARATE SPACES. |
| | ELEC RM, BREAK, STORAGE. |
| | EVEN AS EXISTING, WITH THE SCOPE PF |
| | ELECTRICAL WORK BEING DONE , THESE AREAS |
| | WOULD BE REQUIRED TO MEET CURRNET CODE. |
| | |
| | 8)NOTE: PLEASE INDICATE IF MAIN |
| | ELECTRICAL RM CONTAINS, AN EXISTING EM |
| | LT? IF NOT, ONE WILL BE REQUIRED. |
| | LS 101 7.8, 700.16 ETC. |
| | |
| | 9)NOTE: PLEASE SEE EM LTS ARE REQUIRED |
| | TO BE CIRCUITED TO THE NORMAL LIGHTING |
| | BRANCH CIRCUIT IN ANY ONE AREA. 700.12E. |
| | |
| | 10) NOTE: PLEASE SEE 210.62, 220.12 AS |
| | ANY WINDOW AREAS IN FRONT OF BLDG WILL |
| | REQUIRED "SHOW WINDOW" RECEPTS. |
| | |
| | 11) NOTE: PLEASE VERIFY CONDUCTORS FROM |
| | WHAT WILL BE A TEMP GENERATOR GUTTER. |
| | PLEASE SEE THESE CONDUCTORS ARE SIZED |
| | FOR THE 1600'S AS SHOWN FOR "SB"? |
| | 240.4,310.16 |
| | AS THE GEN IS NOT PART OF THESE PLANS |
| | AND PERMIT AND IS ONLY GOING TO BE |
| | INSTALLED ON A "TEMP BASIS", NO |
| | PROVISIONS ARE PROVIDED FOR LIMITING THE |
| | OCP FOR THE FEEDERS. |
| | |
| | 13) NOTE: PLEASE SEE IF GRND FAULT |
| | PROTECTION IS PROVIDED ON MAIN, PLEASE |
| | SEE THE POSSIBILTY OF AN ISSUE NOT |
| | SWITCHING THE NEUTRAL IN THE MAIN WHEN |
| | USING A GEN WHICH MAY OR MAY NOT HAVE |
| | GRND FAULT. PLEASE SEE 700.7D,700.26, |
| | NFPA-110 6.2.15*, 230.95B |
| | |
| | ** PLEASE COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW |
| | REVISED SHEETS INTO TWO COMPLETE SETS |
| | FOR REVIEW AND STAMPING. PLEASE ONLY |
| | SUBMIT ON SET OF THE OLD/VOIDED REMOVED |
| | SHEETS. |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE IN CONTACTING |
| | THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2006-03-20 00:00:00 | IN ELEC FOR REVIEW |