Date Text
2006-03-21 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE SHEET A.0.1 WHICH
 REFERENCES THE FLORIDA FIRE PREVENTION
 CODE FOR THE ELECTRICAL CODE??
 PLEASE MAKE THE FOLLOWING REFERENCES FOR
 CODES ON ARCHITECTURAL SHEETS AND
 ELECTRICAL SHEETS.
 2002. NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE 2002 NEC 210.8B3 FOR
 KITCHENS IN OTHER THAN DWELLINGS UNITS
 FOR GFI PROTECTION.
  
 3) NOTE: PLEASE CLARIFY SOME FIXTURES
 IE: PLEASE SEE F1 WHICH MENTIONS THIS TO
 BE A PENDANT TYPE OF FIXTURE, HOWEVER
 PLANS INDICATE THESE AS2X4 LAYIN'S??
  
 4) NOTE: PLEASE PROVIDE MANUFEACTURES
 SPECS/CUT SHEETS ON LIGHTING CONTROL
 PANEL/ENERGY MANAGEMENT SYSTEM. PLEASE
 ALSO SUBMIT FOR EM INVERTER PANEL.
 215.5
 PLEASE BE SURE THESE INDICATE THE
 LISTING FROM A NRTL.
  
 5)NOTE; PLEASE PROVIDE SPECS/ CUT
 SHEETS FOR "KIRK KEY INTERLOCK" PLEASE
 PROVIDE INFORMATION THAT THE MAIN
 BREAKER STILL CONTAINS A MANUAL MEANS OF
 DISCONNECT LOCATED ON THE OUTSIDE OF THE
 EQUIPMENT. 230.76.230.79
  
 6)NOTE: PLEASE CALRIFY GROUND FAULT
 PROTECTION BEING INDICATED FOR BOTH
 MAINS. PLEASE SEE 230.95,240.13 ETC AS
 GF PROTECTION IS NOT REQUIRED, HOWEVER
 MAY BE INSTALLED.
 THIS IS ONLY A NOTE AND NO CHANGES ARE
 NEEDED. IF PLANS SHOWS THIS, THEN THEY
 WILL BE REQUIRED TO BE INSTALLED.
  
 7) NOTE: PLEASE SEE FBC CHAPTER 13,
 13-413.1ABC.1, PLEASE SHOW WORST CASE
 SCENARIO FOR VOLTAGE DROP.
 PLEASE PROVIDE INFORMATION ON ROOMS
 WHICH ARE CONSIDERED SEPARATE SPACES.
 ELEC RM, BREAK, STORAGE.
 EVEN AS EXISTING, WITH THE SCOPE PF
 ELECTRICAL WORK BEING DONE , THESE AREAS
 WOULD BE REQUIRED TO MEET CURRNET CODE.
  
 8)NOTE: PLEASE INDICATE IF MAIN
 ELECTRICAL RM CONTAINS, AN EXISTING EM
 LT? IF NOT, ONE WILL BE REQUIRED.
 LS 101 7.8, 700.16 ETC.
  
 9)NOTE: PLEASE SEE EM LTS ARE REQUIRED
 TO BE CIRCUITED TO THE NORMAL LIGHTING
 BRANCH CIRCUIT IN ANY ONE AREA. 700.12E.
  
 10) NOTE: PLEASE SEE 210.62, 220.12 AS
 ANY WINDOW AREAS IN FRONT OF BLDG WILL
 REQUIRED "SHOW WINDOW" RECEPTS.
  
 11) NOTE: PLEASE VERIFY CONDUCTORS FROM
 WHAT WILL BE A TEMP GENERATOR GUTTER.
 PLEASE SEE THESE CONDUCTORS ARE SIZED
 FOR THE 1600'S AS SHOWN FOR "SB"?
 240.4,310.16
 AS THE GEN IS NOT PART OF THESE PLANS
 AND PERMIT AND IS ONLY GOING TO BE
 INSTALLED ON A "TEMP BASIS", NO
 PROVISIONS ARE PROVIDED FOR LIMITING THE
 OCP FOR THE FEEDERS.
  
 13) NOTE: PLEASE SEE IF GRND FAULT
 PROTECTION IS PROVIDED ON MAIN, PLEASE
 SEE THE POSSIBILTY OF AN ISSUE NOT
 SWITCHING THE NEUTRAL IN THE MAIN WHEN
 USING A GEN WHICH MAY OR MAY NOT HAVE
 GRND FAULT. PLEASE SEE 700.7D,700.26,
 NFPA-110 6.2.15*, 230.95B
  
 ** PLEASE COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW
 REVISED SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING. PLEASE ONLY
 SUBMIT ON SET OF THE OLD/VOIDED REMOVED
 SHEETS.
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
  
2006-03-20 00:00:00IN ELEC FOR REVIEW