| Plan Review Notes For Permit 06020501 |
| Permit Number |
06020501 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-14 00:00:00 | | | | | | | DENIED | | | | | | 1) FLORIDA STATE COVER SHEET WAS NOT | | | SUBMITTED AS PART OF PRODUCT APPROVAL | | | FOR STORM PANELS. STORM PANEL DRAWINGS | | | HAVE ALSO BEEN REVISED UNDER THE STATE | | | APPROVAL FOR THE 2004 CODE | | | | | | 2) MARK THE STORM SHUTTER NOA AS TO | | | MOUNTING TYPE (PG.1), ATTACHMENT TYPE | | | (PG.2), TYPE OF FASTENER (PG.4), TYPE OF | | | CONSTRUCTION, EDGE DISTANCE, ETC. | | | | | | 3) THE PGT FLORIDA COVER SHEET HAS BEEN | | | REVISED, SUBMIT UPDATED INFORMATION | | | | | | 4) PROVIDE DOOR OPENING SIZES FOR | | | PRESSURES AND PANEL SIZES | | | | | | 5) PGT DOOR EVALUATION REPORT IS FOR A | | | MAXIMUM 12'-0" DOOR.THE OPENING IS | | | 14'-0" HOW IS THIS OPENING TO BE FRAMED | | | OR POURED, AND ENGINEERED TIE DOWN OR | | | STEEL PLACEMENT WILL BE REQUIRED. ALSO | | | DOES HEIGHT REQUIRE ANY MODIFICATION | | | | | | 6) A RERECORDED COPY OF NOC IS REQUIRED | | | PRIOR TO A PERMIT BEING ISSUED, IT | | | EXPIRES IN 90 DAYS IF WORK HAS NOT | | | COMMENCED | | | | | | | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | |
|