Plan Review Notes
Plan Review Notes For Permit 06020497
Permit Number 06020497
Review Stop M
Sequence Number 1
Notes
Date Text
2006-02-21 00:00:00*** DENIED ***
  
 1) MANUAL 'J' CALCULATIONS ARE MISSING
 FROM THE ENERGY CALCULATIONS, PLEASE
 SUPPLY MANUL 'J' CALCULATIONS.
  
 2) ENERGY CAL'S. NEED SIGNATURE OF
 PERSON PREPARED BY.
  
 3) ENERGY CAL'S. ARE CALLING FOR A 13
 SEER A/C SYSTEM, AND PLANS ARE CALLING
 FOR A 12 SEER SYSTEM THE TWO MUST
 COINCIDE, PLEASE CORRECT.
  
 4) MECHANICAL PLANS MUST SHOW ALL DUCT
 SIZES, GRILL SIZES, AND CFM'S. .
  
 5) RETURN AIR TRANSFER DUCTS MUST BE
 SIZED, SEE NOTE #6.
  
 6)BALANCED RETURN AIR.
 THIS MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (B)TRANSFER GRILLES SHALL USE 50
 SQUARE INCHES (OF GRILLE AREA) TO 100
 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGH-THE-WALL TRANSFER GRILLES AND
 USING AN UNRESTRICTED 1-INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER
 RETURN AIR BALANCE
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 7) SHOW ALL DUCT, AND GRILL SIZES TO NEW
 DUCT WORK FOR FIRST FLOOR.
  
 8) CLOTHES DRYER VENT MUST TERMINATE AT
 LEAST 4 FT. AWAY FROM A/C CONDENSER
 UNITS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.