| 2006-02-21 00:00:00 | *** DENIED *** |
| | |
| | 1) MANUAL 'J' CALCULATIONS ARE MISSING |
| | FROM THE ENERGY CALCULATIONS, PLEASE |
| | SUPPLY MANUL 'J' CALCULATIONS. |
| | |
| | 2) ENERGY CAL'S. NEED SIGNATURE OF |
| | PERSON PREPARED BY. |
| | |
| | 3) ENERGY CAL'S. ARE CALLING FOR A 13 |
| | SEER A/C SYSTEM, AND PLANS ARE CALLING |
| | FOR A 12 SEER SYSTEM THE TWO MUST |
| | COINCIDE, PLEASE CORRECT. |
| | |
| | 4) MECHANICAL PLANS MUST SHOW ALL DUCT |
| | SIZES, GRILL SIZES, AND CFM'S. . |
| | |
| | 5) RETURN AIR TRANSFER DUCTS MUST BE |
| | SIZED, SEE NOTE #6. |
| | |
| | 6)BALANCED RETURN AIR. |
| | THIS MAY BE ACHIEVED BY. |
| | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY |
| | INCREASING THE RETURN TRANSFER ONE AND |
| | ONE HALF TIMES THE CROSS SECTIONAL AREA |
| | (SQUARE INCHES) OF THE SUPPLY DUCT |
| | ENTERING THE ROOM OR SPACE IT'S SERVING |
| | AND THE DOOR HAVING AT LEAST AN |
| | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE |
| | PROPER RETURN AIR BALANCE. |
| | (B)TRANSFER GRILLES SHALL USE 50 |
| | SQUARE INCHES (OF GRILLE AREA) TO 100 |
| | CFM (OF SUPPLY AIR) FOR SIZING |
| | THROUGH-THE-WALL TRANSFER GRILLES AND |
| | USING AN UNRESTRICTED 1-INCH |
| | UNDERCUTTING OF DOORS TO ACHIEVE PROPER |
| | RETURN AIR BALANCE |
| | (C)HABITABLE ROOMS ONLY SHALL BE |
| | REQUIRED TO MEET THESE REQUIREMENTS FOR |
| | PROPER BALANCED RETURN AIR EXCLUDING |
| | BATHROOMS, CLOSETS, STORAGE ROOMS AND |
| | LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY |
| | AIR INTO THE MASTER SUITE SHALL BE |
| | INCLUDED. PER 2004 FBC/R M1602.4 . |
| | |
| | 7) SHOW ALL DUCT, AND GRILL SIZES TO NEW |
| | DUCT WORK FOR FIRST FLOOR. |
| | |
| | 8) CLOTHES DRYER VENT MUST TERMINATE AT |
| | LEAST 4 FT. AWAY FROM A/C CONDENSER |
| | UNITS. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |