2006-02-21 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ARCHTTECT MUST SIGN AND SEAL BOTH
 SETS OF PLANS SUBMITTED FOR REVIEW. SEE
 481.221.
  
 2} THE GROUNDING ELECTRODE CONDUCTOR
 MUST COMPLY WITH 250.66. #4 FOR A 2/0
 COU CONDUCTOR. (200 AMPS.)
  
 3} INDICATE THE AIC RATING OF THE
 SERVICE EQUIPMENT PER 110.9.
  
 4} THE EQUIPMENT GROUNDING CONDUCTOR
 FROM THE NEW 200 AMP DISCONNECT TO THE
 NEW 200 AMP PANEL MUST BE A MINIMUM OF
 #6 CU TO COMPLY WITH 250.122.
  
 5} THE A/C DISCONNECTS SHOWN BEHIND THE
 UNITS DO NOT COMPLY WITH 110.26
 CLEARANCE REQUIREMENTS.
  
 6} SMOKE DETECTORS ARE REQUIRED ON THE
 FIRST FLOOR PER 313.1 FBC. SEE REVIEWED
 PLAN FOR LOCATION.
  
 7} A RECEPTACLE MUST BE ADDED PER 210.52
 IN THE MASTER BEDROOM, SOUTHWEST CORNER.
  
 8} THE WHIRLPOOL MUST HAVE A GFI
 RECEPTACLE OR BREAKER PROTECTION, SPA OR
 HOT TUB SUPPLY RECEPTACLE. RECEPTACLES
 THAT PROVIDE POWER FOR A SPA OR HOT TUB
 SHALL BE GROUND-FAULT
 CIRCUIT-INTERRUPTER PROTECTED. 680.43(3)
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  