| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE ARCHTTECT MUST SIGN AND SEAL BOTH |
| | SETS OF PLANS SUBMITTED FOR REVIEW. SEE |
| | 481.221. |
| | |
| | 2} THE GROUNDING ELECTRODE CONDUCTOR |
| | MUST COMPLY WITH 250.66. #4 FOR A 2/0 |
| | COU CONDUCTOR. (200 AMPS.) |
| | |
| | 3} INDICATE THE AIC RATING OF THE |
| | SERVICE EQUIPMENT PER 110.9. |
| | |
| | 4} THE EQUIPMENT GROUNDING CONDUCTOR |
| | FROM THE NEW 200 AMP DISCONNECT TO THE |
| | NEW 200 AMP PANEL MUST BE A MINIMUM OF |
| | #6 CU TO COMPLY WITH 250.122. |
| | |
| | 5} THE A/C DISCONNECTS SHOWN BEHIND THE |
| | UNITS DO NOT COMPLY WITH 110.26 |
| | CLEARANCE REQUIREMENTS. |
| | |
| | 6} SMOKE DETECTORS ARE REQUIRED ON THE |
| | FIRST FLOOR PER 313.1 FBC. SEE REVIEWED |
| | PLAN FOR LOCATION. |
| | |
| | 7} A RECEPTACLE MUST BE ADDED PER 210.52 |
| | IN THE MASTER BEDROOM, SOUTHWEST CORNER. |
| | |
| | 8} THE WHIRLPOOL MUST HAVE A GFI |
| | RECEPTACLE OR BREAKER PROTECTION, SPA OR |
| | HOT TUB SUPPLY RECEPTACLE. RECEPTACLES |
| | THAT PROVIDE POWER FOR A SPA OR HOT TUB |
| | SHALL BE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTED. 680.43(3) |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |