Plan Review Notes
Plan Review Notes For Permit 06020488
Permit Number 06020488
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-02 00:00:00DENIED
  
 1) 110.1.2* W. P. B. ADMINISTRATIVE
 CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH
 THE PERMIT WAS ISSUED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE
 WITH THE PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED
 IN CHAPTER 6, TABLE 601.
 D) THE DESIGN OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM
 IS REQUIRED.
 F) ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT.
  
 2) FBC11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 SUBMIT AN ITEMIZED BREAKDOWN LISTING THE
 ITEMS AND SHOWING THAT 20% OF JOB COST
 IS BEING SPENT ON ACCESSIBILITY.
  
 3) SPECIFY THE REQUIRED FLAME SPREAD AND
 SMOKE DEVELOPED CLASS OF THE NEW WALL
 AND CEILING FINISHES ON THE PLAN. SEE
 2004 FBC 803.
  
 4) THE DOOR LAYOUT FOR THE NEW OFFICES
 SHWN ON THE OVERALL FLOOR PLAN DIFFERS
 FROM THE WORK AREA FLOOR PLAN. PLEASE
 CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  