| Date |
Text |
| 2006-03-01 00:00:00 | DENIED |
| | |
| | 1) 110.1.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING & FOR CERTIFICATE OF |
| | OCCUPANCY: |
| | A) THE EDITION OF THE CODE UNDER WHICH |
| | THE PERMIT WAS ISSUED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE DESIGN OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM |
| | IS REQUIRED. |
| | F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| | OF THE BUILDING PERMIT. |
| | PLEASE INDICATE THIS INFORMATION ON THE |
| | PLANS. |
| | |
| | 2) THE ADDRESS AND PROPERTY CONTROL |
| | NUMBER ON THE PERMIT APPLICATION AND THE |
| | NOTICE OF COMENCEMENT DO NOT MATCH. THEY |
| | ARE FOR DIFFERENT BUILDINGS AND PARCELS. |
| | PLEASE CORRECT. IF APPLICATION IS |
| | CORRECT RECORD NEW NOC WITH CORRECTIONS. |
| | |
| | 3) INDICATE THE FIRE RATED TENANT |
| | SEPARTION AND CORRIDOR WALLS ON THE |
| | PLAN. |
| | |
| | 4) SPECIFY THE FLAME SPREAD AND SMOKE |
| | DEVELOPED CLASS OF THE INTERIOR WALL AND |
| | CEILING FINISHES THAT WILL BE INSTALLED. |
| | SEE 2004 FBC 803. |
| | |
| | 5)11-4.1.6(2) DUTY TO PROVIDE AN |
| | ACCESSIBLE PATH OF TRAVEL TO ALTERED |
| | AREAS SHALL BE DEEMED DISPROPORTIONATE |
| | TO THE OVERALL ALTERATION WHEN THE COST |
| | EXCEEDS 20 % OF THE COST OF THE ALTERA- |
| | TION TO THE PRIMARY FUNCTION AREA. |
| | (A)(I) AN ACCESSIBLE ENTRANCE |
| | (II) AN ACCESSIBLE ROUTE |
| | (III) AT LEAST ONE ACCESSIBLE REST- |
| | ROOM FOR EACH SEX OR A SINGLE |
| | UNISEX RESTROOM |
| | (IIII) ACCESSIBLE TELEPHONE |
| | (IV) ELEMENTS SUCH AS PARKING, STOR- |
| | AGE OR ALARMS. |
| | -FBC 11-4.13.6 EXISTING DOOR AT COPY |
| | ROOM IS REQUIRED TO HAVE MANEUVERING |
| | CLEARANCE OF A MINIMUM OF 18" OF WALL |
| | SPACE AT THE LATCH ON THE PULL SIDE OF |
| | DOOR. |
| | |
| | - FBC 11-4.22.2 EXISTING BATHROOM DOOR |
| | SHALL NOT SWING INTO THE CLEAR FLOOR |
| | SPACE REQUIRED FOR ANY FIXTURE. |
| | |
| | SUBMIT ITEMIZED COST BREAKDOWN LISTING |
| | THE ITEMS AND COSTS SHOWING THAT 20% OF |
| | $1200 OR $2400 HAS BEEN ALLOCATED TO |
| | MEETING ACCESSIBILITY REQUIREMENTS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |