Plan Review Notes For Permit 06020466
Permit Number 06020466
Review Stop G
Sequence Number 1
Notes
Date Text
2006-03-06 00:00:00DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PERMIT:
  
 1. GAS PERMIT CANNOT APPROVED WITH OUT
 ZONING APPROVAL OF GENERATOR LOCATION.
 2. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 3. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES. UNDERGROUND
 GALVANIZED PIPE NOT APPROVED PER SEC.
 404.8, 404.8.2.
 7. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 (NOTE: ON SUBMITTED DRAWING THERE ARE
 TWO INDCATED DELIVERY PRESSURES ONE OF
 12" WC AND THE OTHER 2PSI. WHAT IS THE
 DELIVERY PRESSURE YOU WANT TO USE?)
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721