| Plan Review Notes For Permit 06020466 |
| Permit Number |
06020466 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-03-06 00:00:00 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | THE FOLLOWING INFORMATION IS REQUIRED | | | FOR GAS PERMIT: | | | | | | 1. GAS PERMIT CANNOT APPROVED WITH OUT | | | ZONING APPROVAL OF GENERATOR LOCATION. | | | 2. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS. | | | 3. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES. UNDERGROUND | | | GALVANIZED PIPE NOT APPROVED PER SEC. | | | 404.8, 404.8.2. | | | 7. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | | (NOTE: ON SUBMITTED DRAWING THERE ARE | | | TWO INDCATED DELIVERY PRESSURES ONE OF | | | 12" WC AND THE OTHER 2PSI. WHAT IS THE | | | DELIVERY PRESSURE YOU WANT TO USE?) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY MIKE PERSON | | | (561)805-6730 | | | FAX (561)805-6731 | | | E-MAIL [email protected] | | | UNDER SUPERVISION OF K.STEVENS | | | (561)805-6721 |
|