2006-02-27 00:00:00DENIED:
  
 1) FIRE ALARM SYSTEM SHALL CLASS A,
 STYLE D OR FULLY ADDRESSABLE.
  
 2) FIRE ALARM SYSTEM SHALL BE UL
 CERTIFICATED FOR CENTRAL STATION SERVICE
 AND HAVE DOCUMENTS ATTESTING TO THIS
 CERTIFICATION PRIOR TO FINAL FIRE
 INSPECTION.
  
 3) DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM IN THE CITY OF WEST
 PALM BEACH.
  
  