| Plan Review Notes For Permit 06020406 |
| Permit Number |
06020406 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-04-17 00:00:00 | DENIED; | | | | | | 1.BATHROOMS DO NOT APPEAR TO MEET THE | | | FBC-2004 CHAPTER 11 ACCESSIBITY CODE. | | | PLEASE SHOW DETAIL WITH TURNING RADIUS | | | AND CLEAR FLOOR SPACE. | | | 2.FBC-2004 PLUMBING TABLE 403.1 MINIMUM | | | PLUMBING FIXTURES REQUIRES A DRINKING | | | FOUINTAIN NONE SHOWN. | | | 3.SHOW WATER AND SEWER CONNECTIONS. | | | BACKFLOW PROTECTION REQUIRED ON WATER | | | SERVICE. | | | 4.INFORMATION NEEDED FROM GENERATOR; | | | MANUFACTURE SPEC SHEETS,SIZE AND TYPE OF | | | FUEL IT WILL USE. | | | 5.SITE PLAN AND FIRE LEGEND DRAWINGS ARE | | | NOT THE SAME. GENERATOR AND BATHROOM | | | LOCATIONS ARE DIFFERENT. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|