| 2006-03-06 00:00:00 | ************UNSAT ************ |
| | |
| | 1)NOTE: PLEASE SEE NOT ENOUGH |
| | INFORMATION WAS SUBMITTED FOR ELECTRICAL |
| | PLANS. |
| | |
| | 2)NOTE:PLEASE SEE NO RISER, PANEL |
| | SCHEDULES, LOAD CALCUALTIONS ETC. |
| | 215.5 |
| | |
| | 3)NOTE: PLEASE SUBMIT SPECS FOR |
| | GENERATOR UNIT AND HOW THIS WILL CONNECT |
| | INTO ELECTRICAL SYSTEM. |
| | |
| | 4)NOTE: PLEASE PROVIDE LAYOUT FOR SALES |
| | OFFICE FURNITURE. |
| | |
| | 5)NOTE: PLEASE VERIFY ALL CIRCUITING FOR |
| | EM/ EXT LTS PER 700.12E. |
| | PLEASE SEE NO PERMANENT LIGHTING OR |
| | EMERGENCY LTS ARE SHOWN?? |
| | PLEASE PROVIDE MIN LIGHTING PER LS 101 |
| | 7.8, 7.9.2.2 |
| | |
| | 6)NOTE: PLEASE SEE PLANS SUBMITTED |
| | CONTAINING TITLE BLOCKS FOR ENGINEER , |
| | SHALL BE SIGNED, DATED AND SEAL AS |
| | REQUIRED PER FS 471.025 |
| | PLEASE SEE REVIEW COMMENTS FROM OTHER |
| | TRADES WHICH MAY REQUIRE PLANS. |
| | |
| | 7)NOTE: PLEASE SUBMIT ELECTRICAL |
| | PLANS/DETAIL FOR REVIEW UNDER THE 2002 |
| | NEC, LS 101 ETC |
| | |
| | 8)NOTE: PLEASE SEE MISSING LICENS |
| | INFORMATION REQUIRED ON TITLE BLOCKS FOR |
| | ENGINEERING FIRM. PER FLORIDA |
| | ADMININSTRATIVE CODE 61G15-23.002, |
| | FLORIDA STATUES, 471.023 |
| | |
| | 9)NOTE: PLEASE SEE VALUATION SHALL |
| | INCLUDE ALL LABOR AND MATERIALS FOR |
| | COMPLETE SCOPE OF WORK FOR TIME IN-USE, |
| | 108.3 FBC ADMINISTRATIVE CODE AS AMENDED |
| | BY THE CITY OF WEST PALM BEACH. |
| | |
| | 10)NOTE: PLEASE SEE COMMENS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL |
| | PLANS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW ONCE ALL REVIEWS ARE COMPLETED. |
| | IF THERE ARE ANY QUESTIONS, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE. |
| | |