| 2006-05-03 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | 1.)CERTIFICATE OF AUTHORIZATION NUMBER |
| | FOR THE PROFESSIONAL ASSOCIATION IS |
| | REQUIRED, FAC61G15-23.002. |
| | |
| | 2.)EACH SHEET IS TO BE SEALED OR AN |
| | INDEX SHEET IS REQUIRED, |
| | FAC61G15-23.002.YOU HAVE INCLUDED AN |
| | INCOMPLETE TABLE OF CONTENTS.ADDRESS. |
| | |
| | 3.)THE LETTER DATED FEBRUARY 1, 2006 |
| | FROM DAVIS ENGINEERS PA TO WEST PALM |
| | BEACH REFERS TO 20TH FBC RATHER THAN |
| | 2004 FBC (TYPO). |
| | |
| | 4.)PROVIDE A SITE PLAN WHICH SHOWS |
| | COMPLIANCE WITH FBC TABLE 602, |
| | FBC3103.3..A SITE PLAN WAS PROVIDED |
| | BUT DOES NOT INCLUDE DIMENSIONS TO THE |
| | PROPERTY LINE OR TO THE FUTURE SALES |
| | OFFICE TRAILER. |
| | |
| | 5.)THE LETTER DATED FEB 1,2006 |
| | PROVIDES A WIND DESIGN CRITERIA OF 90MPH |
| | WITH REMOVAL OF THE FABRIC AT 75MPH. |
| | THE CITY OF WEST PALM BEACH IS IN THE |
| | 140MPH ZONE.THE ENTIRE STRUCTURE IS TO |
| | BE STRUCTURALLY COMPLIANT FOR THIS WIND |
| | ZONE, FBC1609, FBC3102.7. |
| | |
| | 6.)PROVIDE WIND DESIGN INFORMATION |
| | FBC1603.1.4.NOTE THAT THIS PARCEL HAS |
| | ALREADY BEEN DETERMINED TO BE EXPOSURE C |
| | BY OTHER DESIGN PROFESSIONALS. |
| | |
| | 7.)DECLARE AN OCCUPANCY, FBC CHAPTER |
| | 3. |
| | |
| | 8.)THE LETTER STATES THAT THE SOIL |
| | CONDITIONS ARE SIMILAR TO THE DORAL |
| | PROJECT.THE LETTER FROM THE SOILS |
| | ENGINEER STATES THAT THERE IS A LIMEROCK |
| | SUBSTRATE.THIS AREA DOES NOT HAVE A |
| | LIMEROCK SUBSTRATE.A SOILS REPORT IS |
| | AVAILABLE FOR THIS SITE.CONSULT WITH |
| | THE SOILS ENGINEER FOR THIS PROJECT TO |
| | JUSTIFY YOUR DESIGN RATHER THAN |
| | ENGINEERING FROM ANOTHER PROJECT. |
| | |
| | 7.)ANY SUPPORTING DOCUMENTS PREPARED |
| | BY AN ENGINEER AND SUBMITTED FOR PUBLIC |
| | RECORD ARE TO BE SIGNED, SEALED, DATED |
| | ORIGINALS, FAC61G15-23.002. |
| | |
| | 8.)FLAME RESISTANCE IS TO BE IN |
| | ACCORDANCE WITH NFPA 701.THE |
| | CERTIFICATE PROVIDED IS DATED 2002, |
| | STATES THAT IT IS FILED WITH CALIFORNIA, |
| | AND DOES NOT REFER TO NFPA 701.IT ALSO |
| | STATES THAT IT COVERS MATERIALS REFERRED |
| | TO ON THE REVERSE SIDE, BUT THAT SIDE IS |
| | BLANK.PLEASE ADDRESS. |
| | |
| | 9.)PROVIDE THE EXIT DOOR DIMENSION, |
| | FBC10. |
| | |
| | 10.)SHOW THE SIDEWALK WIDTH AND THE |
| | SLOPE (ACCESSIBLE ROUTE), |
| | FBC11-4.1.2(2).NOTE THAT THE SITE PLAN |
| | STATES THAT THERE IS A SLOPE IN THE |
| | GRADE. |
| | |
| | 11.)PROVIDE THE ELEVATION ON BOTH |
| | SIDES OF THE DOOR, FBC11-4.1.2. |
| | |
| | 12.)PROVIDE DETAILS FOR THE BATHROOM; |
| | TURNING RADIUS, DIMENSIONS FOR THE SINK |
| | AND TOILETS, GRAB BARS, ETC.THE FLOOR |
| | PLAN DOES NOT MATCH THE ELEVATION. |
| | |
| | 13.)THE FLOOR PLAN DIFFERS FROM THE |
| | SITE PLAN IN THE BATHROOM LOCATION. IF |
| | THE BATHROOM IS LOCATED TEN FEET AWAY AS |
| | SHOWN, PROVIDE INFORMATION IN REGARDS TO |
| | THE ACCESSIBLE ROUTE.A RAMP IS SHOWN |
| | ON AN ELEVATION, WHAT IS THIS FOR? |
| | |
| | 14.)INFORMATIONAL ONLY; NEW COMMENTS |
| | ARE LIKELY UPON RESUBMITTAL DUE TO THE |
| | LACK OF COMPLETE INFORMATION. |