2006-04-04 00:00:00PROVISO:
  
 1.PER 2004 FMC 1302.3 PIPE MATERIAL
 FOR FUEL OIL PIPING SHALL BE IN
 ACCORDANCE WITH TABLE 1302.3,
 NONMETALLIC PIPE - ASTM D2996.
 THE SUBMITTAL FOR THE SPECIFICATION OF
 THE FUEL OIL PIPING INDICATES ASTM
 D2310.THIS SHOULD READ ASTM D2996 AS
 THE STANDARD.ASTM D2310 IS A
 CLASSIFICATION UNDER ASTM D2996 &
 RTRP-11AF REFERENCES THE DESIGNATION
 CODE.THE MARKING OF THE PIPE SHALL
 COMPLY WITH ASTM D2996 SUB-SECTION 10.
  